This paper presents the construction of a permanent magnets synchronous generator model. The computational methodology and the basic results of electromagnetic calculations of the synchronous generator with permanent magnets are presented. On the basis of the calculations conducted, a physical model of the generator was made, on which the preliminary laboratory tests were carried out. A comparative record sheet of the preliminary laboratory tests and the results of the theoretical calculations are also included in the paper. The main advantage of presented model of a permanent magnets synchronous generator is low output voltage variability.
Jednym z posdtawowych elementów opisu jakości napiecia jest ocena zmienności jego wartości skutecznej. Obecnie używane są dwie miary zmienności napięcia: wskaźniki wahań napiecia oraz wskaźniki krótkookresowego Pst i Długookresowego Plt migotania światła. Miara wahania napięcia opisuje amienność wartości skutecznej za pomocą amplitudy i częstości wahania. Wskaźniki Pst i Plt wykorzystane sa do oceny stopnia uciążliwości migotania swiatła. W referacie zamieszczono porównanie obu miar wykazując, oprócz różnic definicyjnych, różne możliwości diagnostyczne.
EN
One of the principal elements useful in voltage quality description is estimating changes of the rms values of voltage. Currently two measures of such changes are in use, i.e. indexes of voltage fluctuations and short-term and long-term measures of light flickering. Pst and Pit are utilized in evaluation of light flickering noxiousness. In the paper comparison of both measures is presented. Basides differences in their definition, various diagnostic tests have been also shown.
The paper presents four measures of voltage variability in a power grid: a short-term flicker Pst indicator, voltage fluctuation U with f indices, maximum Umax, and minimum Umin rms voltage values as well as δV10 index. The major features of these measures have been listed. Dependences of these measures values on voltage variability have been shown on diagrams. An exemplary voltage variability assessment has been conducted basing on the measurement results recorded in a low voltage circuit. In the example, using the Umax and Umin values, it has been stated that the recorded changes of voltage, its rises and falls, can be causing interference in the work of receivers. Moreover, large values of (Umax - Umin) differences may be a reason of large voltage variability occurrence. The analysis of Pst = f (t) time plot confirmed the occurrence of obnoxious voltage fluctuation in one phase. It has led to the final statement that the voltage quality failed to meet legal and standard requirements. Moreover, the values of voltage fluctuation indices δU and f have been determined, which made it possible to estimate the properties of the voltage variability source.
PL
W pracy przedstawiono cztery miary zmienności napięcia w sieci elektroenergetycznej: wskaźnik krótkookresowego migotania światła Pst, wskaźniki wahań napięcia δU i f, wartości maksymalne Umax i minimalne Umin napięcia oraz wskaźnik δV10. Wymieniono podstawowe cechy tych miar. Graficznie zobrazowano zaleźności wartości tych miar od zmienności napięcia. Na podstawie wyników pomiarów zarejestrowanych w obwodzie nn przeprowadzono przykładową ocenę zmienności napięcia. Wykorzystując wartości Umax i Umin uznano, że zarejestrowane zmiany napięcia, wzrosty i zaniżenia, mogą być przyczyną zakłóceń w pracy odbiorników. Ponadto duże wartości różnic (Umax - Umax) zwróciły uwagę na możliwość wystąpienia dużej zmienności napięcia. Analizując przebieg czasowy Pst = f (t) wykryto wystąpienie uciążliwych wahań napięcia w jednej fazie. Na tej podstawie stwierdzono niezachowanie jakości energii elektrycznej w ujęciu prawnym i normatywnym. Określono wartości wskaźników wahań napięcia: amplitudy δU i częstości f. Uzyskano w ten sposób informacje o parametrach źródła zmienności napięcia.
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.