At one of Polish steelworks there was carried out an experiment, which aim was measure-ment of voltage fluctuation parameters at the same point of supply network, by means of different measuring instruments, than on that basis assessment of credibility of ten selected flickermeters, available on the Polish market. AU instruments were dedared by the manufacturers as complying with the terms of the IEC 61000-4-15 standard Their indications however, differ significantly as the cxperi-ment has demonstrated. The authors do not assess the correctness of indications of specific instruments, rather conclude their substandal discrepancy. Obtained results indicate that the recommendations of IEC 61000-4-15 standard allow for construction of correct, i.e. complying with the standard, instruments which do not meet their primary metrological objective (comparison of measuremcnt results). Normally a uscr of the instrument cannot evaluate hunself the correctness of measurements while manufacturer's declara-tion does not guarantee their correctness, as the experiment has demonstrated.
2
100%
PL
W referacie przeanalizowano pracę układów odpowiedzialnych za skalowanie wejściowego sygnału napięcia sieciowego oraz jego przetwarzanie do postaci cyfrowej. Analizę wykonano uwzględniając zalecane przez normy częstotliwościowe pasmo wejściowe miernika oraz biorąc pod uwagę możliwość pojawienia się wahań napięcia i migotania światła na skutek występowania wyższych harmonicznych i interharmonicznych napięcia w sieci energetycznej.
EN
In this paper functioning of scaling and analog to digital conversion systems have been analyzed. The analysis has been done taking into consideration the frequency band given in the standard and the influence of harmonics and interharmonics of network voltage on appearing voltage fluctuations and flicker.
3
Content available remote Dobór przetwornika napięcia dla miernika migotania światła
100%
PL
W artykule przeanalizowano wykorzystanie czterech różnych przetworników napięci do skalowania sygnału pomiarowego w mirniku migotania światła. Zamieszczono wyniki pomiarów oraz uzyskane błędy. Do testów użyto komputerowy system pomiarowy zbudowany w środowisku LabView, który realizuje funkcje generatora oraz miernika migotania światła.
EN
In this paper the use of four different voltage transducers for scaling the measuring signal in the flickermeter have been analyzed. The obtained results and errors have been described. The tests were done with a computer measurement system, which was built using LabView. The system realizes functions of the generator and the flickermeter.
|
|
tom z. 66
69-70
EN
The new edition of IEC 61000-4-15 has brought some changes in the implementation and testing requirements of flicker meters as a part of power quality analyzers. This article describes the software which was made to test the flicker parameter at the power quality analyzers according to updated IEC 61000-4-15.
|
|
tom Vol. 14, iss. 2
7--12
EN
Phase disturbances in electric power signals are neglected and only amplitude (envelope) distortions are discussed in a literature. Amplitude disturbances are interpreted as Amplitude Modulation (AM) of main 50 Hz frequency. Detailed analysis of all disturbances and their sources are presented in the paper. It is shown that AM and narrow band PM (phase modulation) take place in power network simultaneously and those two modulations interact with each other. Voltage variation is proposed as disturbances measurement. Theoretical results are verified by field experiments and their results are presented.
PL
W pracy przedstawiono analizę działania toru sygnałowego flickermetru dla napięcia wejściowego składającego się z trzech składowych: o częstotliwości podstawowej oraz dwóch sub/interharmonicznych. Dla takiego napięcia wejściowego zbudowano matematyczny model flickermetru Za pomocą tego modelu wyznaczono zależność wskaźnika Pst od składowych sub/interharmonicznych o częstotliwościach pomijanych w literaturze przedmiotu. Wykazano możliwość powstawania uciążliwego migotania światła dla składowych interharmonicznych o dużych częstotliwościach. Określono wpływ faz początkowych składowych sub/interharmonicznych na wynik pomiaru Pst. W celu weryfikacji analizy porównano wyniki badań modelowych i symulacji numerycznych.
EN
An analysis of the flickermeter signal chain for the input voltage consisting of three components: the fundamental frequency fc, and the two sub/interharmonics of the frequency fm, and fn, respectively, are presented in the paper. For the purpose of model tests a simplification of the flickermeter block diagram were proposed. A mathematical model was built, consisting of a set of equations describing the dependence of Pst indicator of the amplitude of sub/interharmonics, and the initial phase of one of these components. The model equations were derived for seven areas of the fn - fm plane. The dependence of the Pst indicator on sub- and interharmonics was identified for frequencies that are skipped in the related literature. It was demonstrated that the flicker could occur for interharmonics of frequencies that are significantly higher than 100 Hz, and for subharmonics of frequencies that are less than 15 Hz. A range of frequencies of subharmonics were designated for which it is necessary to take into account the phase relations while determining the Pst indicator. The results of model tests were compared with the results of numerical simulation of the IEC flick-ermeter signal chain.