The arc suppression coil determines whether it can effectively extinguish the arc when it is grounded in the neutral non-effective grounding system. An artificial grounding test is an importantway to verify its performance. In this study, 13 substations with the 10 kV system in the Ningxia areawere selected and considered. Based on the artificial single-phase grounding test, the residual current, the compensation current and the off-resonance degree were measured in the arc suppression coil, and the performance of the arc suppression coil in the 10 kV system was verified. The experimental results show that the error of arc suppression coil automatic measurement is large, the off-resonance degree is large, the resistive component in the compensation current is excessive, the harmonic component exists in the compensating current and capacitive current. To solve these problems, this paper puts forward the corresponding countermeasures for reference.
In an electronic device, the current supplied to the electrodes is related to different types of processes inside the device: current density, change in spontaneous polarization, and change in dielectric properties. Two expressions for the electrode current are derived: one is based on the time derivative of the Shockley-Ramo theorem, the other on the time derivative of the dielectric tensor. This result is illustrated for a switching liquid crystal device and a two-dimensional flux tube.