In this paper the thermal cycle model of supercritical power plant conjugated with the cooling system working at different operating conditions was presented. The calculations for reference unit of 600 MW output with close cooling system were made. The basic parameters and construction type of cooling tower and condenser were assumed. The algorithm for cooling system consists of the cooling tower model and condenser model was presented. The iteration process to calculate the parameters of thermal cycle and cooling water cycle was described. The influence of atmospheric temperature changes typical for the one-year period on the power plant performance indicators was discussed. The results were presented and the investigations were summed up.
PL
Przedmiotem niniejszej analizy jest dobór parametrów oraz konfiguracji układu chłodzenia dla bloku ultra-nadkrytycznego o mocy 900 MW. Analizę pracy skraplacza oparto o amerykańską normę Heat Exchange Institute. Przedstawione badania obejmują porównanie dwóch wariantów układu chłodzenia, które dotyczą konfiguracji równoległej oraz szeregowej pracy skraplacza. Układ równoległy jest powszechnie stosowany, a rozdzielenie strumienia wody chłodzącej na poszczególne skraplacze bądź sekcje skraplacza daje w nich jednakowe warunki kondensacji. W przypadku konfiguracji szeregowej całkowity strumień wody chłodzącej przepływa szeregowo przez skraplacz pierwszy, a następnie trafia do skraplacza drugiego. Takie rozwiązanie w stosunku do układu równoległego powoduje wzrost sprawności obiegu wynikający z obniżenia całkowitego ciśnienia w skraplaczu. Konfiguracja szeregowa powoduje, że obniżeniu ciśnienia w pierwszej sekcji skraplacza towarzyszy nieznaczny wzrost ciśnienia w drugiej sekcji skraplacza. Stąd też pole powierzchni wymiany ciepła drugiej sekcji skraplacza jest często zwiększone w celu poprawy warunków kondensacji. Niniejsza praca stanowi uzupełnienie oraz rozszerzenie przedstawionych w literaturze analiz. Dotyczy to w szczególności dokładnego uwzględnienia wpływu straty wylotowej turbiny niskoprężnej na wartość uzyskiwanych przyrostów sprawności obiegu cieplnego w przypadku konfiguracji szeregowej pracy skraplacza.
EN
The aim of this paper is the selection of parameters and configuration of the cooling system of 900 MW ultra-supercritical power unit. The performed analysis of the condenser was based on the Heat Exchange Institute standard. The presented studies include comparison of two variants of cooling water system. Both, the parallel and serial configuration of the condenser was investigated. Parallel cooling water system is widely used, and the separation of the cooling water stream into individual sections of the condenser or condensers give equal conditions of condensation. In the case of a serial configuration, the total flow of cooling water flows through the first condenser and then it goes to the second condenser. This causes the decrease of pressure in the first and increase of pressure in the second condenser. Hence, the heat exchange surface area of the second condenser is often increased to improve the conditions of condensation. This paper extends the analyzes presented in the literature. It particularly concerns the investigation of influence of the exhaust loss for obtained efficiency gains in case of the serial configuration of condenser.
EN
Solving AeroAcoustics (CAA) problems by means of the Direct Numerical Simulation (DNS) or even the Large Eddy Simulation (LES) for a large computational domain is very time consuming and cannot be applied widely for engineering purposes. In this paper in-house CFD and CAA codes are presented. The in-house CFD code is based on the LES approach whereas the CAA code is an acoustic postprocessor solving non-linearized Euler equations for fluctuating (acoustic) variables. These codes are used to solve the pressure waves generated aerodynamically by a flow over a rectangular cavity and by the vortex street behind a turbine blade. The obtained results are discussed with respect to the application of the presented numerical techniques to pressure waves modeling in steam turbine stages.
EN
The paper is concerned with an important issue from the field of thermoacoustics - the numerical modelling of the flow field in the thermoacoustic engine. The presented way of modelling is based on the solution to fundamental fluid mechanics equations that govern the flow of compressible, viscous, and heat-transferring gas. The paper presents the way of modelling the thermoacoustic engine, the way of conducting calculations and the results which illustrate the correctness of the selected computational technique.
EN
The paper presents a thermal-economic analysis of a 900 MW coal-fired power unit for ultra-supercritical parameters with internal steam reheat. The subject of the study was the cycle proposed as the "initial thermal cycle structure" during the completion of the project "Advanced Technologies for Energy Generation" with the steam parameters of 650/670 [degrees]C/30 MPa. Two configurations of internal reheat were analysed: with a fourand seven-section exchanger. The effect of reheat on the operation of the power unit under a partial load was also analysed, and preliminary calculations of the heat exchange area of the internal reheat were made.
PL
W artykule przeprowadzono analizę warunków pracy obiegu cieplnego bloku nadkrytycznego. Uwzględniono w niej sprzężenie obiegu cieplnego z obiegiem wody chłodzącej. Przedstawiono model obiegu cieplnego oraz algorytm jego rozwiązania, model skraplacza oraz model chłodni kominowej mokrej o ciągu naturalnym. Analizowano również pracę układu cieplnego i układu wody chłodzącej w zmiennych warunkach. Do analizy zastosowano obieg referencyjny siłowni na nadkrytyczne parametry pary o mocy 600MW. Dla tego bloku założono parametry zamkniętego układu chłodzenia, przyjęto wymiary skraplacza oraz gabaryty chłodni kominowej. Analizowano różne warianty pracy bloku, uwzględniające różne parametry powietrza atmosferycznego. Rozważono również możliwość regulacji obiegu wody chłodzącej w celu określenia optymalnych, ze względu na sprawność cieplną siłowni, warunków pracy pomp. Przedstawiono wyniki obliczeń dla założonych charakterystyk poszczególnych elementów układu i sformułowano wnioski.
EN
In this paper the thermal cycle model of supercritical power plant conjugated with the cooling system working at different operating conditions was presented. The calculations for reference unit of 600 MW output with close cooling system were made. The basic parameters and construction type of cooling tower and condenser were assumed. The algorithm for cooling system consists of the cooling tower model and condenser model and enables calculations for different working regimes. The iteration process to calculate the parameters of thermal cycle and cooling water cycle was described. The influence of atmospheric temperature changes typical for the one-year period on the power plant performance indicators and cooling water control possibilities were discussed. The chosen results were presented and the investigations were summed up.