Water supply system (WSS) is characterized by its continuous work and requires high reliability level for its operating as well as for its safety System operating is inseparably connected with the possibility that different failures (undesirable events) occur. The most often they have random character and then they can be described by the classical methods used in the reliability engineering including the probabilistic methods but sometimes they are the consequences of the events which can cause the catastrophic situation. Events of this type cause the so called domino effect that is a chain of the undesirable events which very often develops according to some definite scenarios. In many cases the consequences of such events can be very serious for water consumers as well as for water pipe companies. The basic measure describing WSS safety is risk and the elaboration of the model to analyze risk connected with WSS will allow to use the safety barriers properly. The paper presents paradigms of risk analysis in WSS in the aspect of improving safety for water consumers.
2
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
W artykule opisano instalację zasilania pieca łukowego prądu przemiennego. Elektryczny piec łukowy AC, ze względu na dynamiczny charakter pracy łuku elektrycznego, negatywnie oddziałuje na sieć zasilającą w postaci generowania wyższych harmonicznych, wahań napięcia oraz asymetrii. Przedstawiono wybrane wyniki pomiarów przeprowadzonych po stronie niskiego napięcia, gdzie nieliniowe prądy łuków są źródłem zaburzeń oraz w punkcie wspólnego przyłączenia sieci wysokiego napięcia. Instalacja pieca łukowego na poziomie średniego napięcia wyposażona jest w trójgałęziowy pasywny filtr wyższych harmonicznych, który spełnia podwójną funkcję: redukcji harmonicznych oraz kompensacji mocy biernej dla składowej podstawowej. Analizę pracy pieca łukowego AC przeprowadzono dla pełnego cyklu wytopu stali obejmującego stany roztapiania (pierwszy i drugi kosz złomowy) oraz rafinacji stali.
EN
The article presents the AC power supply installation. The AC electric arc furnace, due to the dynamic nature of the electric arc work, has a negative effect on the supply network in the form of generating higher harmonics, voltage fluctuations and asymmetries. Selected results of measurements on the low-voltage side are presented, where non-linear arc currents are a source of disturbances and at the high-voltage network connection point. The installation of an arc furnace at the medium voltage level is equipped with a three-branch passive higher harmonics filter, which has a dual function: harmonics reduction and reactive power compensation for the basic component. The analysis of AC arc furnace operation for the full steel smelting cycle including melting (first and second scrap bin) and refining is shown.
3
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
W artykule opisano zjawiska zachodzące w obwodzie wielkoprądowym elektrycznego pieca łukowego AC. Odwzorowano wpływ zmian długości kolumny łukowej na parametry modelu matematycznego Pentegowa łuku elektrycznego wykorzystującego statyczną charakterystykę napięciowo-prądową. W wyniku symulacji otrzymano dynamiczne charakterystyki napięciowo-prądowe łuków elektrycznych. Na podstawie analizy danych pomiarowych przedstawiono wpływ asymetrii i zaburzeń łuku na jakość energii elektrycznej w układzie zasilania AC-EAF.
EN
The article describes the phenomena occurring in the high-current circuit of an AC electric arc furnace. The effect of changes in the arc column length on the parameters of the Pentegov mathematical model of the electric arc based on static voltage-current characteristics is mapped. As a result of the simulation, dynamic voltage-current characteristics of electric arcs were obtained. Based on the analysis of measurement data, the effect of asymmetry and arc disturbances on the quality of electricity in the AC-EAF power system is presented.
Elektryczny piec łukowy AC, ze względu na dynamiczny charakter pracy łuku elektrycznego, negatywnie oddziałuje na sieć zasilającą w postaci generowania wyższych harmonicznych, wahań napięcia oraz asymetrii. W artykule przedstawiono analizę asymetrii napięć i prądów w instalacji zasilania pieca łukowego AC. Na podstawie zarejestrowanych komputerowo danych pomiarowych obliczono za pomocą szybkiej transformaty Fouriera podstawowe harmoniczne przebiegów napięć i prądów w poszczególnych punktach toru zasilania. Następnie wyznaczono współczynniki asymetrii napięć i prądów oraz średnie wartości impedancji fazowych na poziomie niskiego i średniego napięcia dla stanów roztapiania i rafinacji.
EN
The electric AC arc furnace, due to the dynamic nature of the electric arc operation, has a negative impact on the supply network in the form of generating higher harmonics, voltage fluctuations and asymmetry. The paper presents the analysis of asymmetry of voltages and currents in the power supply installation of an AC arc furnace. The basic harmonics of voltage and current waveforms at individual points of the power line were calculated using the Fast Fourier Transform on the basis of computer-recorded measurement data. Next, the voltage and current asymmetry coefficients as well as mean values of phase impedances at the low and medium voltage levels were determined for the melting and refining states.