2013 | R. 89, nr 10 | 217-220
Tytuł artykułu

An Online Monitoring System of Corona Loss of High Voltage Transmission Lines Based on Metalized Membrane Method

Wybrane pełne teksty z tego czasopisma
Warianty tytułu
PL
Monitorowanie on-line strat ulotu w liniach wysokiego napięcia bazujące na wykorzystaniu metalizowanej membrany
Języki publikacji
EN
Abstrakty
EN
An online monitoring system of corona loss of high voltage transmission lines based on metalized membrane method is developed in this paper. The system includes 3 components: the upper computer, the conductor voltage acquisition module and the corona leakage current acquisition module. The corona leakage current acquisition module is set on the high voltage line. The transmission line is covered by a certain length of thin metalized membrane . The sampling resistance is put paralleling between metal layer and bundle conductor. The conductor voltage acquisition module is set in transformer substation. The two modules are synchronized by the rising edge of Pulse Per Second (PPS) emitted by Global Position System (GPS), and the data is sent to the public port of mobile telephone network by General Packet Radio Service (GPRS). The remote upper computer gets the data and calculates corona loss of each bundle conductor by visiting public port. The experiment results show that the system can monitor the corona loss accurately. The whole study is helpful in the further research of UHV transmission line’s corona in different environment and weather.
PL
Zaprezentowano metodę monitorowania strat powodowanych ulotem (wyładowaniem koronowym) w liniach transmisyjnych wysokiego napięcia. Do tego celu wykorzystano metalizowaną membranę. Układ składa się z trzech modułów: komputera, systemu akwizycji napia) ęcia i systemu akwizycji prądu ulotu. Linia transmisyjna jest pokryta na pewnej długości cienką metalizowaną membraną. Do lokalizacji ulotu zastosowano moduł GPS a do transmisji danych moduł GPRS.
Wydawca

Rocznik
Strony
217-220
Opis fizyczny
Bibliogr. 10 poz., rys., wykr.
Twórcy
autor
autor
  • Xi’an Jiaotong University
  • Xiamen Electric Power Company
autor
  • Xi’an Jiaotong University
autor
  • Xi’an Jiaotong University
autor
  • Xi’an Jiaotong University
autor
  • National Engineering Laboratory for UHV Engineering Technology
autor
  • National Engineering Laboratory for UHV Engineering Technology
autor
  • Shaanxi Electric Power Research Institute
autor
  • Shaanxi Electric Power Research Institute
Bibliografia
  • [1] Zhenya Liu, “Ultra-high voltage grid,” Beijing:China economic publishing house, 2005. (in Chinese)
  • [2] R. D. Stearns and T. D. Bracken. “Corona and electric field performance of BPA prototype 1200kV transmission line, ” CIGRE, 1981, 232- 06.
  • [3] D. E. Perry, V. L. Chartier and G. L. Reiner. “BPA 1100 kV Transmission System Development Corona and Electric Field Studies,” IEEE Trans. Power App. Syst., vol. PAS-98, no. 5, pp 1728 – 1738,1979.
  • [4] E. R. Taylor, N. Kolcio and W. E. Pakala, “The Apple Grove 750-kV Project-775-kV Radio Influence and Corona Loss Investigations,” IEEE Trans. Power App. Syst., vol. PAS-84, no. 7, pp 573 – 579, 1965.
  • [5] N. Kolcio, V. Caleca, Marmaroff, S.J. and et al., “Radio-Influence and Corona-Loss Aspects of AEP 765-kV Lines,” IEEE Trans. Power App. Syst., vol. PAS-88 , no. 9, pp 1343–1355,1969.
  • [6] S, Frans, M. Andrew, R. Klas and et al., “Evaluation, verification and operational supervision of corona losses in Sweden,” IEEE Trans. Power Del.,vol. PWRD-22,no. 2, pp 1210- 1217,1984.
  • [7] C. Francis Harding, “Corona Losses between Wires at High Voltages,” Transactions of the American Institute of Electrical Engineers, vol. XXXI, no. 1, pp 1035 – 1049, 1912.
  • [8] X. B. Liang, M. R. Raghuveer, O. C. Norris- Elye and et al., “Corona Loss Measurement on Loaded Operating DC Lines,” IEEE Trans. Instr. and Meas., vol. 37, no. 3, pp 153-155. 1988.
  • [9] H. C. Zhang, Q. Zhang, Y. F. Luo and et al., “Feasibility Study of Metalized Membrane Method Applied to Monitoring Corona Loss of AC/ DC Transmission Line,” Proceedings of 1st International Conference on Electric Power Equipment- Switching Technology. Xi’an, China. 2011, October 23-27. Page 253-257.
  • [10] R. J. (Bud)Bates, “GPRS: Gerneral Packet Radio Service,” McGraw-Hill Companies, 1998.
Typ dokumentu
Bibliografia
Identyfikatory
Identyfikator YADDA
bwmeta1.element.baztech-dc21f8fc-6b54-4dd7-9121-28e25c93ee65
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.