Odpowiedź dielektryczna celulozy impregnowanej różnymi cieczami izolacyjnymi
Języki publikacji
Abstrakty
The dielectric response of cellulose in the form of paper and pressboard was investigated. Samples of pressboard were impregnated with different insulating liquids: new and aged transformer oil and synthetic ester. The research was done for two groups of pressboard with about 5% and 0.5% moisture content. Samples of non-impregnated paper were investigated during drying process. Obtained data were analyzed using Havriliak-Negami relaxation function. The results can be useful for moisture evaluation in impregnated cellulose insulation.
W artykule przedstawiono badania odpowiedzi dielektrycznej celulozy w postaci papieru i preszpanu. Preszpan był impregnowany różnymi cieczami izolacyjnymi (nowym i starzonym olejem transformatorowym, estrem syntetycznym). Badania przeprowadzono dla preszpanu o zawilgoceniu 5% i 0,5%. Próbki nieimpregnowanego papieru były badane podczas procesu suszenia. Otrzymane dane przeanalizowano z wykorzystaniem funkcji relaksacji Havriliaka-Negamiego. Rezultaty mogą być przydatne dla oceny zawilgocenia izolacji celulozowej.
Czasopismo
Rocznik
Tom
Strony
223-225
Opis fizyczny
Bibliogr. 10 poz., tab., wykr.
Twórcy
autor
- Politechnika Poznańska, Instytut Elektroenergetyki, ul. Piotrowo 3A, 60-965 Poznań, andrzej.graczkowski@put.poznan.pl
Bibliografia
- [1] Moser H.P., Dahinden V., Transformerboard II, H. Weidmann AG, Switzerland, (1997)
- [2] Saha T.K., Review of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers, IEEE Trans. Diel. and El. Ins., 10 (2003), n.5, 903-914
- [3] Gubanski S.M. et al., Reliable diagnostics of HV transformer insulation for safety assurance of power transmission system REDIATOOL – a European research project, CIGRE, D1-207, Paris, (2006)
- [4] Ekanayake C., Gubanski S.M., Graczkowski A., Walczak K., Frequency response of oil impregnatem pressboard and paper samples for estimating moisture in transformer insulation, IEEE Trans. Power Delivery, 21 (2006), n.3, 1309-1317
- [5] Gockenbach E., Borsi H., New insulating liquids for high voltage apparatus, IEEE Intern. Conf. Dielectric Liquids, (2008)
- [6] Borsi H., Gockenbach E., Dolata B., Ester fluids as alternative for mineral based transformer oil, IEEE Intern. Conf. Dielectric Liquids, (2008)
- [7] Gubanski S.M. et al ., Dielectric response methods for diagnostics of power transformers, IEEE Electr. Insul. Mag., 19, (2003), n.3, 12-18
- [8] Linhjell D., Lundgaard L., Gäfvert U., Dielectric Response of Mineral Oil Impregnated Cellulose and the Impact of Ageing, IEEE Trans. Diel. and El. Ins., 14 (2007), n.1, 156-169
- [9] Graczkowski A., Influence of impregnating oil on di electric response of oil-paper insulation, 21st Nordic Insulation Symposium, Gothenburg, (2009), 171-173
- [10] Kremem F., Schonhals A., Broadband Dielectric Spectroscopy, Springer-Verlag, Berlin Heidelberg, (2003)
Typ dokumentu
Bibliografia
Identyfikatory
Identyfikator YADDA
bwmeta1.element.baztech-article-BPOH-0061-0005