Fault location finding in power system is very important problem in power system monitoring. Moreover, demand for high grid availability are crucial for TSOs contracts. Many scientific papers are published on mentioned theme, along with efforts in transmission and distribution system operators about improving fault location accuracy. Recently, signal processing methods like Wavelets and Hilbert-Huang Transform are introduced in fault location procedure. In this paper, a new approach to power system fault signal processing is proposed. Three-phase fault voltages are converted to the vector of absolute values of its complex-space phasor. This vector represents fault traveling wave and it is further processed for fault location finding with Hilbert-Huang transform. The simulation results show that proposed method allows better accuracy in comparison to earlier procedures.
PL
Lokalizacja zwarć w liniach przesyłowych jest ważna z punktu widzenia prawidłowego funkcjonowania linii przesyłowych. W ostatnim czasie zaproponowano wiele metod lokalizacji zwarć za pomocą falek czy transformaty Hilberta-Huanga. W tym artykule proponujemy przekształcenie trójfazowych sygnałów napięciowych za pomocą wektora przestrzennego. Rezultaty symulacji wykazują poprawę dokładności lokalizacji zwarć tą metodą w porównaniu z wcześniej opisanymi algorytmami.