In this paper, physical model of typical defects in GIS are established, and their PD characteristics are studied using pulsed-current method. The results show that the PRPD patterns, time domain waveforms, average amplitude and central-phase changing of PD signals are quite different between different types of defects while have very similar distribution characteristics within the same kind of defect. Thus effective recognition of PD types and deeper study of the mechanism of PD would be possible based on the result of this paper.
PL
Przedstawiono model fizyczny typowego defektu łącznika gazowego GIS a jego charakterystykę wyładowania niezupełnego badano stosując impulsy prądowe. Rezultaty pokazują, że przebieg w dziedzinie czasu, średnia amplituda i zmiana fazy sygnału są różne dla różnych typów defektów ale mają podobną charakterystykę rozkładu dla podobnego defektu. To pozwala na skuteczne rozpoznawania defektu i analizę mechanizmu jego powstawania.
2
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
Izolacja transformatorów w przekształtnikach jest narażona na napięcia AC i DC. Przeprowadzono analizę wyładowań niezupełnych w izolacji z papieru olejowego w systemach napięcia stałego z obecnością składowej przemiennej. Zarejestrowano wyładowania przy użyciu oscyloskopu o paśmie 5 GHz. Badania przeprowadzona dla napięcia DC, AC oraz DC plus AC. Impulsy prądu wyładowań mają inną amplitudę, czas narastania i energię w zależności od rodzaju napięcia. Istotną sprawą jest napięcia. Zaproponowano efektywna metodą monitorowania jakości izolacji transformatorów w przekształtnikach.
EN
The insulation of converter transformer is stressed by AC and DC voltages. To investigate partial discharge (PD) characteristic of oilpaper insulation, this paper designed a power source system of DC superimposed AC voltage. The testing sample is an air gap model in the middle of an insulation cardboard. A broadband current transformer is used to measure PD current recorded by an oscilloscope with a bandwidth of 5 GHz. Experiments are performed under AC,DC only, and DC superimposed AC voltages with the sample immersed in transformer oil using electrode configurations that is parallel plate. The single PD pulses are anglicized by ORIGIN software. It is realized that the impulse current signals generated due to partial discharges under AC and DC voltages are different with amplitude, rise time, counts, duration and energy content PD pulse under AC voltage is of long duration pulse compared to that generated under DC voltage, and the PD pulse under DC superimposed AC voltage is stochastic. The key point is the moment (phase position) PD occurring moves to the zero point of the applied voltage than the case only under ac voltage. These will contribute to the development of effective PD monitoring systems for oil-insulated converter transformer.
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.