Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników

Znaleziono wyników: 5

Liczba wyników na stronie
first rewind previous Strona / 1 next fast forward last
Wyniki wyszukiwania
help Sortuj według:

help Ogranicz wyniki do:
first rewind previous Strona / 1 next fast forward last
EN
The aim of this paper is to detect the single line to ground fault on the unit generator- transformer. A new ground fault detection scheme based on the extraction of energy and statistical parameters from wavelet transform based neural network is proposed. The faulty current signals obtained from a simulation were decomposed through wavelet analysis into various approximations and details. The simulation of the unit generator-transformer was carried out using the Sim-PowerSystem Blockset of MATLAB. The energy and statistical parameters analysis involved measured of the dispersion factors (range and standard deviation) of wavelet coefficients. Regarding the ANN performance, the errors in the SLGfault detection of ANN were under 1 %. The results indicate that the proposed algorithm was accurate enough in differentiating a single line to ground fault and un-fault for a unit generator-transformer.
PL
Przestawiono metodę detekcji nieprawidłowości w uziemieniu jednostki generator-transformator. W nowej metodzie wykorzystano transformatę falkową I sieć neuronową. Symulację przeproprowadzno wykorzystując Sim-PowerSystem Blockset of MATLAB. Uzyskano błąd pomiaru poniżej 1%.
EN
This paper presents accurate fault detection and location using wavelet based on Clarke’s transformation. This study was done using Clarke’s transformation method to convert current phase (three phase) signal into a two-phase current alpha and beta (current mode). The proposed method introduced the mode current to transform the signal using discrete wavelet transform (DWT) and was utilized to obtain the wavelet transform coefficients. Analysis was also conducted for other mother wavelets. The most accurate parent was wavelet Db8, with the fastest time of detection and the smallest error, whereas the largest error was found in Coil4 parent wavelet. The result for proposed method was compared with Db4, Sym4, Coil4 and Db8 and found to be very accurate.
PL
W artykule opisano dokładną metodę wykrywania awarii w sieciach przesyłowych bazująca na falkowej transformacie Clarka. Sygnał trójfazowy jest przekształcany do postaci dwufazowej Za najbardziej się do tego celu nadająca uznano falkę Db8 z najszybszym czasem wykrywania i najlepszą dokładnością. Wyniki porównano z innymi typami falek.
3
Content available remote Ground Fault Protection Methods of a Generator Stator
EN
The type of generator grounding method and the system configuration determine the choice of ground fault protection. Ground fault generator stator can cause serious damage to the generator. Therefore, the total area of the generator stator windings must be protected against hazardous condition. Because the conventional methods are unable to separate ground faults close to the neutral point of view, there should be a method to protect entire stator winding. The paper discusses ways to discern ground faults for the generator stator. Some suggestions are proposed that can help in ensuring the generator stator ground fault more accurate.
PL
Stojan wirnika generatora powinien być szczególnie chroniony przed zagrożeniami. Konwencjonalne metody nie są w stanie oddzielić błąd uziemienia w pobliżu punktu neutralnego. W artykule opisano metody zabezpieczeń stojana generatora przed błędami uziemienia.
4
Content available remote Comparative Study on Optimum DG Placement for Distribution Network
EN
With the advent of restructuring in power system and the exponential growth in the load demand, the importance of Distribution Generation (DG) has been increased. The DG is used to reduce the power losses and also to improve the system stability. The non-optimum DG placement and sizing could result in increase power losses and instability of the power system. This paper presents the comparative study for DG allocation techniques based on three different indicators namely Active power VSI (P-VSI), Reactive power VSI (Q-VSI) and Power Losses Reduction (PLR) indicator. The performances of these indicators are also compared for optimal DG output, maximum loss reduction, improvement in voltage profile and improvement in voltage stability. Standard 12-bus and 33-bus radial distribution networks are used as a test system. From the analysis and results, it is found that PLR performance is better than P-VSI and Q-VSI indicators in DG allocation.
PL
W artykule przedstawiono analizę porównawczą technik alokacji kogeneracji rozproszonej, opartych na trzech wskaźnikach: mocy czynnej falownika, mocy biernej falownika oraz redukcji strat mocy. W warunkach optymalnej pracy dokonano porównania maksymalnej możliwej redukcji strat, jakości profilu napięcia oraz stabilności napięcia wybranych metod. W testach systemów uwzględniono standardową 12 i 33-liniową sieć dystrybucji energii. Przedstawiono wnioski końcowe analizy.
EN
This paper present a novel optimization method, Time Varying Acceleration – Rank Evolutionary Particle Swarm Optimization (TVAREPSO) in solving optimum generator sizing for minimising power losses in the transmission system of South Sulawesi, Indonesia. A comparison between the proposed method and three other methods was done in order to find the best method to optimize the generators’ output size. The results show that the TVA-REPSO algorithm can obtain the same performance as PSO but it only required shorter computing time and can converges faster than the original PSO.
PL
W artykule przedstawiono matematyczną metodę rozwiązania zagadnienia znalezienia optymalnego rozmiaru generatora, w celu minimalizacji strat w elektroenergetycznym systemie przesyłowym Południowej Sulawesi w Indonezji. W algorytmie wykorzystano optymalizację roju cząstek ze zmiennym w czasie przyspieszeniem (ang. TVA-REPSO). Dokonano porównania z innymi metodami, pokazało, że opracowana metoda ma skuteczność podobną do klasycznej metody PSO, lecz krótszy czas obliczeń.
first rewind previous Strona / 1 next fast forward last
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.