Dissolved Gas Analysis (DGA) is a vital tool for monitoring power transformer conditions. Despite its effectiveness, current interpretation techniques lack consistency and often rely on personnel experience, leading to varied conclusions for the same oil sample. This paper proposes a fuzzy logic approach to standardize DGA interpretation, aiming to establish a uniform method for critical transformer ranking and informed asset management decisions. The approach integrates existing DGA interpretation techniques into an expert model, enhancing reliability. The model, developed from 338 oil samples, offers a consistent and accurate basis for transformer condition assessment and asset management.
PL
Analiza rozpuszczonego gazu (DGA) jest niezbędnym narzędziem do monitorowania stanu transformatorów mocy. Pomimo swojej skuteczności, obecne techniki interpretacji nie są spójne i często opierają się na doświadczeniu personelu, co prowadzi do różnych wniosków dla tej samej próbki oleju. W niniejszym artykule zaproponowano podejście oparte na logice rozmytej w celu standaryzacji interpretacji DGA, mające na celu ustanowienie jednolitej metody klasyfikacji krytycznych transformatorów i świadomych decyzji dotyczących zarządzania aktywami. Podejście to integruje istniejące techniki interpretacji DGA w eksperckim modelu, zwiększając niezawodność. Model opracowany na podstawie 338 próbek oleju oferuje spójną i dokładną podstawę do oceny stanu transformatorów i zarządzania aktywami.