The practice of operating reactive power compensation systems involving passive multiple filter circuits (FC) configured by single–tuned filters has shown, that it’s energizing can cause damage of the filter components. Impact of feasible FC configurations, including FC with a C–type filter, on switching overvoltages and overcurrents under the harmonic filters energizing were analyzed. Influence of the filters tuning on transient behavior has been shown. The transient analysis has been carried out by simulating of the FC within Matlab/Simulink software.
2
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
Distribution transformers protection method against high frequency transients generated during Vacuum Circuit Breaker (VCB) operations is presented in this paper. ATP/EMTP simulations of transients generated during the VCB operation and protection method effectiveness is described. In addition prototype windmill installation is presented. For simulations realistic VCB model was used enabling one to study both prestrikes, generated during the contact making process as well as re-ignitions generated during the contact breaking.
PL
W artykule przedstawiono metodę ochrony transformatorów dystrybucyjnych przed wysokoczęstotliwościowymi przepięciami generowanymi podczas operacji łączeniowych z użyciem wyłączników próżniowych. W artykule przedstawiono symulacje komputerowe przepięć generowanych zarówno podczas załączania jak i wyłączania transformatorów. Symulacji dokonano przy użyciu pakietu ATP/EMTP. Zaprezentowano również przykładową istniejącą instalację opisanych w artykule urządzeń.