Content available Generator split-phase protection
EN
The stator winding of a hydrogenerator is often made up of coils with multiple turns in the same slot. It is therefore possible for faults to develop between adjacent turns on the same phase (turn-toturn faults). These faults cannot be detected by the stator differential protection because there is no difference between the neutral- and terminal-side currents. Split-phase protection, an overcurrent element responding to the difference between the currents in the winding parallel branches, is typically provided to detect these faults. Ideally, the split-phase element should be sensitive enough to detect a single shorted turn. Despite the fact that the current in this turn can be six to seven times the machine nominal current, the current seen by the split-phase protection can be quite small, in the order of one-twentieth of the generator full-load current. In addition, a spurious split-phase current can be measured due to current transformer (CT) errors, saturation during external faults in particular. Therefore, primary considerations in the application of split-phase protection are the method of measuring the difference in the currents between the parallel branches and the proper selection of the CT used for this purpose.
first rewind previous Strona / 1 next fast forward last
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.