Content available remote Monitoring of electric arc furnace supply voltage frequency using phasor analysis
EN
This paper presents the results of measurement experiment conducted in the operating steel plant. Frequency analysis of measured signals revealed an interesting phenomenon, as it happened that after switching off the electric arc furnace, the frequency of the supplying voltage and current increased slightly instead of decreasing, as we would normally expect. This abnormal frequency behaviour was identified by phasor analysis and also confirmed by the DTFT (Discrete Time Fourier Transform) analysis, and the MatrixPencil analysis.
PL
Artykuł prezentuje wyniki eksperymentu wykonanego w hucie stali. Analiza częstotliwości ujawniła ciekawe zjawisko, w którym po wyłączeniu pieca łukowego częstotliwości napięcia i prądu w wewnętrznej części huty zmniejszyła się zamiast zwiększyć, jak można by się spodziewać. To nieoczekiwane zjawisko zostało zarejestrowane z pomocą PMU i potwierdzone przez transformację Fouriera dla sygnałów dyskretnych oraz analizę MatrixPencil.
PL
Artykuł prezentuje wyniki eksperymentu wykonanego w hucie stali. System pomiarowy wykorzystany do przeprowadzenia pomiarów jest oparty na systemie czasu rzeczywistego z układem FPGA, który pozwala na wykonanie pomiarów sygnałów analogowych. Trzy fazy napięcia i prądu zostały zmierzone w trzech wybranych punktach sieci zasilającej. Analiza częstotliwości ujawniła ciekawe zjawisko, w którym po wyłączeniu pieca łukowego częstotliwości napięcia i prądu w wewnętrznej części huty zmniejszyła się zamiast zwiększyć, jak można by się spodziewać. To nieoczekiwane zjawisko zostało zarejestrowane z pomocą PMU i potwierdzone przez analizę MatrixPencil. Przeprowadzone pomiary potwierdziły zasadność monitorowania częstotliwości napięcia zasilania pieców łukowych za pomocą analizy fazora.
EN
This paper presents the results of measurement experiment conducted in the operating steel plant. The measurement system was built with real time system with FPGA module, capable of measuring analog signals. Three phase voltages and currents were acquired in three selected points of supplying power network. Frequency analysis of measured signals revealed an interesting phenomenon, as it happened that after switching off the electric arc furnace, the frequency of the supplying voltage and current increased slightly instead of decreasing, as we would normally expect. This abnormal frequency behavior was identified by phasor analysis and also confirmed by DTFT (Discrete Time Fourier Transform) analysis, and MatrixPencil analysis. Performed measurements proved phasor analysis to be a useful application for electric arc furnace frequency monitoring.
EN
To maintain power system operation in a balanced and stable condition, the frequency deviation and the rate of frequency change information are highly desired in monitoring and protection applications of the power grid. How to obtain frequency information more accurately and efficiently has been the topic discussion for decades. PMUs (Phaser Measurement Unit) are the most widely-used devices for measuring phase angle differences and they also provide very accurate frequency information. However, the high installation cost of PMUs limits their applications for wide area control and stability analysis of power system. Thanks to commercial GPS receivers and the fast developments in Ethernet networks, an affordable wide area, quasi real-time, GPS synchronized frequency measurement is now possible. This paper introduces a portable networked Frequency Disturbance Recorder (FDR) device, which can be used at any 110V wall outlet and transmit measured frequency data remotely via the Ethernet. The practical issues and challenges of the device design and implementation are analyzed and discussed. Based on these low cost FDRs, a US-wide Frequency Network (FNET) has been implemented at Virginia Tech and some power system monitoring applications are being developed by taking fully advantage of the FDRs.