The induction motor is a most important drive in the production area. These motors are used in various industrial applications. They can be protected from the different mechanical and electrical faults using different protection systems. The protection is very important to detect abnormal motor running conditions such as over current, over voltage, overload, over temperature, and unbalance conditions. In the classical protection systems, the time delay is adjusted constantly without considering the fault level. This paper presents protection system for induction motor based on Sugeno Inference. The time delay is computed by this intelligent protection for different faults. The obtained results are interesting and show the interest of the proposed intelligent protection.
PL
W artykule zaprezentowano system zabezpieczeń silnika indukcyjnego bazujący na Sugeno Inference. Określano opóźnienie czasowe dla różnych rodzajów błędów. W stosunku do istniejących systemów proponowany system umożliwia bardziej precyzyjne określenie błędów.
2
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
The paper presents the method of creating a model in Matlab software of a vacuum circuit breaker that is used for modelling the switching processes of capacitive circuits. In the model of the vacuum circuit breaker, the phenomena of contact bounces (which is a new solution), the phenomenon of the current interruption and also the reconstruction of the strength between the contacts were taken into account during control of the switching process. There are different methods of modelling a circuit breaker for switching circuits proposed in literature, but none of them consider the phenomenon of contact bounces. The solution presented by the author is not ideal. However, in a simple and accessible way it takes into account the aforementioned phenomenon in switching processes. The paper indicates that the used solution is important and influences the waveforms of currents and voltages in circuits during switching processes. The paper also presents voltage and current waveforms that show the method of the model operating during overvoltages and overcurrents. An analysis of emerging overvoltages and overcurrents, and their influence on switching phenomena in the circuit with switching capacitor banks, can also be found in the paper. The most important is included a new version of a model of vacuum circuit which is an answer to simulate a switch on process in capacity MV circuit. In the literature can usually be found the model when we can simulate a switch off MV inductive circuit, so presented model is new version of modelling such capacity circuits.
PL
W pracy przedstawiono metodę tworzenia modelu w oprogramowaniu Matlab wyłącznika próżniowego, który służy do modelowania procesów łączeniowych w obwodach pojemnościowych. W modelu wyłącznika próżniowego uwzględniono zjawisko odbijania styków (które jest nowym rozwiązaniem), zjawisko przerwania prądu, a także rekonstrukcję siły między stykami, podczas sterowania procesem przełączania. Istnieją różne metody modelowania wyłącznika dla układów łączeniowych zaproponowane w literaturze, ale żaden z nich nie uwzględnia zjawiska odbijania styków. Rozwiązanie przedstawione przez autora nie jest idealne. Jednak w prosty i przystępny sposób uwzględnia to zjawisko w procesach przełączania. Dokument wskazuje, że zastosowane rozwiązanie jest ważne i wpływa na przebiegi prądów i napięć w obwodach podczas procesów przełączania. W artykule przedstawiono również przebiegi napięcia i prądu, które pokazują metodę działania modelu podczas przepięć i przetężeń. W artykule przedstawiono analizę pojawiających się przepięć i przetężeń oraz ich wpływ na zjawiska łączeniowe w obwodzie z bateriami kondensatorów. Najważniejszym i nowym rozwiązaniem w modelowaniu łączników próżniowych jest uwzględnienie zjawiska odbicia styków w procesie załączania obwodu pojemnościowego.
Series of tests were conducted in which short-circuit current was registered. Four different overcurrent protection devices were used for a set value of prospective current. Based on obtained data the short-circuit time was calculated. In order to obtain this information a procedure was developed. Later it was implemented with the help of numerical computation software Scilab. In this paper results of calculations, the procedure itself and its implementation are presented.
4
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
Analysis of transient phenomena occurring in the capacitive circuit with a vacuum switch. Paper presents the simulation results performed in ATP/EMTP. The analysis applies to the overvoltage and overcurrent during re-ignitions of arc when surge protection installed is. An assess of the practical suitability and effectiveness of examined system’s connections. The results obtained during the modeling are consistent with the theoretical analysis and empirical research described in the literature.
PL
Artykuł przedstawia analizę zjawisk stanów nieustalonych zachodzących podczas łączenia łącznikiem próżniowym obwodów o charakterze pojemnościowym. Zamieszczono wyniki symulacji przeprowadzonych w programie ATP/EMTP. Przeanalizowano skuteczność, a także przydatność ochrony przeciwprzepięciowej w tychże obwodach. Analiza wyników uzyskanych podczas modelowania jest zgodna z analizami teoretycznymi i badaniami empirycznymi zamieszczonymi w fachowej literaturze.
Łączenie pojemności baterii kondensatorów wywołuje stany przejściowe w danym obwodzie, prowadzące do znacznych przetężeń prądowych oraz przepięć, zarówno przy załączaniu jak i przy ich wyłączaniu baterii kondensatorów, linii kablowych i napowietrznych. Wyłączaniu prądów pojemnościowych towarzyszą znaczne wartości chwilowe napięć międzystykowych łącznika, co może być przyczyną występowania pomiędzy stykami wyłącznika zapłonów ponownych późnych. Załączanie pojemności wywołuje na ogół znaczne przetężenia prądowe w danym obwodzie. Mogą być one przyczyną uszkodzenia kondensatorów załączanej baterii kondensatorów, lub powodować sczepienia się styków łącznia elektrycznego. Przetężenia prądowe oraz sposoby ich ograniczania występujące w takich układach są przedmiotem referatu.
EN
Connecting capacitances of capacitor batteries causes transient states in a given circuit leading to significant overcurrent and overvoltage in both cases i.e. at switching on an off of batteries in cable and open-wire lines. Switching off capacitance currents is accompanied by high actual values of contact potential difference which may cause late reignitions between contacts of switches. Connection of capacitance generates usually significant overcurrent in a given circuit. This may be a reason of failures in capacitors of a capacitance battery being connected or may cause contact tacking in electric switches. The issues of overcurrent and methods of its limitation in such electric circuits are subject matter of this paper.
Artykuł ukazuje zagadnienie wpływu właściwości dynamicznych zadajnika sygnałów wielofazowych na proces testowania urządzeń EAZ (elektroenergetyczna automatyka zabezpieczeniowa). Publikacja zawiera krótką charakterystykę obiektu (urządzenie EAZ), oraz obecnie stosowane metody testowania. Zaprezentowano wyniki badań symulacyjnych, w tym optymalny zestaw nastaw dla obiektu o zadanych parametrach dynamicznych. Właściwy dobór nastaw pozwolił na skrócenie czasu testowania, bez pogorszenia jakości.
EN
This paper presents the impact of multiphase signals generator parameters on electrical power protection devices testing process. Publication include a short presentation of electrical protection devices and testing methods. Obtained results of simulation tests (parameters matrix) are presented. Optimization of multiphase signals generator parameters influences testing time and quality. Słowa kluczowe: urządzenia EAZ, kalibrator, zabezpieczenie nadprądowe, zabezpieczenie zwarciowe, mikroprocesorowy sterownik polowy.
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.