In commonly used short-circuit current calculation methodology, the acceptance of a short-circuit site in the middle of their length leads not only to a significant overestimation of short-circuit currents, but also does not guarantee the selective coordination of electrical apparatus and its proper protection function against electrical shock. The paper presents new approach to the problem of calculation short-circuit current in parallel cables. It is proven that the worst case scenario is highly influenced by the number of cables connected in parallel.
PL
W powszechnie stosowanej metodologii obliczania prądu zwarciowego przyjmuje się, że miejsce zwarcia występuje w środku ich długości co prowadzi nie tylko do znacznego przeszacowania prądów zwarciowych, ale również nie gwarantuje selektywnej koordynacji aparatury elektrycznej i jej odpowiedniej ochrony przed porażeniem elektrycznym. W artykule przedstawiono nowe podejście do problemu obliczeniowego prądu zwarciowego w przewodach równoległych. Udowodniono, że w najgorszym przypadku duzy wpływ ma liczba połączonych równolegle kabli.