The paper shows how fixed-parameters reactive compensators in four-wire systems with a nonsinusoidal voltage can be converted into controlled-parameters compensators. Such compensators can serve as adaptive balancing compensators of reactive power of unbalanced loads. Thyristor switch inductors (TSIs) are used for such conversion. The fixed-parameters balancing reactive compensators are synthesized using the Currents’ Physical Components (CPC) – based power theory. The adaptive compensator is composed of two sub-compensators, one in the structure and the other in the structure. The method is illustrated with a numerical example and results of computer modeling of the load with a fixed-parameters and with an adaptive compensator.
PL
Artykuł pokazuje jak równoważący kompensator reaktancyjny prądu biernego, o sta łych parametrach, w systemach cztero- przewodowych, może być przekształcony w kompensator o parametrach kontrolowalnych. Kompensator taki może być użyty jako kompensator adaptacyjny. Przekształcenie takie umożliwiają włączane tyrystorami induktory (TSI). Parametry równowa żącego kompensator prądu biernego mogą być obliczone z pomocą teorii mocy opartej na Składowych Fizycznych Prądu (CPC). Kompensator jest zbudowany z dwóch sub-kompensatorów, z którch jeden ma strukturę X, a drugi strukturę Y. Przedstawiona w artykule metoda syntezy jest ilustrowana przykładami liczbowymi i rezultatami kompensacji.
EN
The CPC-based power theory (PT) of electrical circuits and systems provides an interpretation of the energy transfer-related physical phenomena in such systems and fundamentals for their compensation. It has been developed, step-by-step, with partial results published in Polish, German, English and American journals and in conference proceedings, often not reported on the main databases and consequently, difficult to be found. Its development was a reaction for the lack of progress in long-lasting attempts aimed at explanation of the energy transfer-related physical phenomena and the lack of fundamentals for compensation in electrical systems with nonsinusoidal voltages. This Review provides a draft of the whole CPC concept with references to more detailed results and a concise historical background and critical comments on other power theories.
PL
Teoria mocy obwodów i systemów elektrycznych, oparta na koncepcji Składowych Fizycznych Prądów, tworzy podstawę teoretyczną dla interpretacji zjawisk fizycznych towarzyszących przesyłowi energii w takich układach i ich kompensacji. Była ona rozwijana stopniowo, z cząstkowymi wynikami publikowanymi w czasopismach polskich, niemieckich, angielskich i amerykańskich oraz w materiałach konferencyjnych, często trudnych do odnalezienia. Rozwój CPC był odpowiedzią na brak postępu w badanich nad teorią mocy i na brak podstaw kompensacji w układach z napięciami niesinusoidalnymi. Przegląd ten jest skrótem CPC, z odnośnikami do bardziej szczegółowych wyników oraz z tłem historycznym i krytycznymi uwagami dotyczącymi wyników innych teorii mocy.
3
Content available remote Reactive Compensation of LTI Loads in Three-Wire Systems at Asymmetrical Voltage
EN
The paper presents fundamentals of design of reactive compensators for total compensation of the reactive and unbalanced currents of linear time invariant (LTI) loads supplied with asymmetrical sinusoidal voltage in three-wire systems. Theoretical fundamentals for the presented method are provided by the Currents’ Physical Components (CPC) based power theory. Development of the reactive compensator equation is the very core of the method presented. A draft of the CPC-based power theory of LTI loads in three-wire systems with asymmetrical, but sinusoidal supply voltage is also presented in the paper.
PL
Artykuł przedstawia podstawy projektowania kompensatorów reaktancyjnych prądu biernego i niezrównoważenia liniowych i czasowo niezmienniczych (LTI) odbiorników trójfazowych zasilanych sinusoidalnym, lecz niesymetrycznym napięciem. Teoretyczne podstawy kompensacji oparte są na Teorii Mocy Składowych Fizycznych Prądów (ang.: Currents’ Physical Components (CPC) – based Power Theory). Głównym elementem przedstawionej metody jest równanie kompensatora reaktancyjnego. Artykuł przedstawia także zarys teorii mocy liniowych czasowo niezmienniczych odbiorników trójfazowych zasilanych niesymetrycznym napięciem sinusoidalnym.
PL
Odbiorniki trójfazowe są niekiedy zasilane napięciem niesymetrycznym, jednak obecny stan rozwoju elektrotechniki nie pozwala opisywać takich odbiorników równaniem mocy, to jest relacją wiążącą wszystkie moce odbiornika. Można to obecnie robić tylko w sposób przybliżony, przyjmując, że napięcie zasilania jest symetryczne. Uniemożliwia to także projektowanie kompensatorów reaktancyjnych, redukujących moc bierną i moc niezrównoważenia w warunkach zasilania napięciem niesymetrycznym. Przedmiotem niniejszego artykułu jest eliminacja tego ograniczenia elektrotechniki poprzez wyprowadzenie równania mocy odbiorników trójfazowych zasilanych napięciem niesymetrycznym oraz przedstawienie podstaw konstrukcji kompensatorów reaktancyjnych odbiorników pracujących w takich właśnie warunkach.
EN
Three-phase loads are sometimes supplied with asymmetrical voltage, however, the present state of electrical engineering does not allow for describing them with a power equation, meaning with a relationship between all powers. It can be done only at the assumption that the supply voltage is symmetrical. It makes impossible of designing reactive compensators for the reactive power and the unbalanced power compensation for the load balancing. The development of the power equation of loads with asymmetrical supply voltage and fundamentals of reactive compensation of such loads is the subject of this paper.