The analysis presented in this paper aims at the determination of the possibilities of detecting network load imbalance on the basis of standard measurements of electric power quality in transformer stations. The imbalance of the load represented by imbalance coefficient directly affects the number of voltage events in the network. The term events used here denotes voltage dip and swell beyond the range stated in the limits. On the basis of the definition of voltage dispersion and imbalance coefficient the relation between the phenomena was established. On the basis of statistical analysis of the results of the measurements the applicability of the voltage measurements in transformer station for the determination of load imbalance in the network was assessed.
PL
Artykuł zawiera wybrane wyniki pomiaru odchyleń wartości napięcia sieci niskiego napięcia od wartości znamionowych. Analiza wyników pomiarów pozwoliła na określenie wpływu niesymetrycznego obciążenia sieci reprezentowanego przez współczynnik asymetrii napięcia na liczbę zdarzeń i głębokość zapadów napięcia występujących u odbiorców, ze szczególnym uwzględnieniem dwóch poziomów napięcia znamionowego - 220 V i 230V.