Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników

Znaleziono wyników: 18

Liczba wyników na stronie
first rewind previous Strona / 1 next fast forward last
Wyniki wyszukiwania
Wyszukiwano:
w słowach kluczowych:  izolatory kompozytowe
help Sortuj według:

help Ogranicz wyniki do:
first rewind previous Strona / 1 next fast forward last
1
Content available remote Surge Breakdown Voltage Study of Contaminated Medium Voltage Composite Insulators
EN
Some issues related to the surge impulse strength of MV line composite insulators with visible contamination deposits have been discussed in the article. Additionally, the resistance of composite insulators to bird droppings (surface degradation) together with the impact of these deposits on surge impulse strength have been verified by laboratory experiments.
PL
W artykule przedstawiono zagadnienia związane z napięciem udarowym wytrzymywanym izolatorów kompozytowych eksploatowanych w liniach średniego napięcia, na których zaobserwowano widoczne osady zabrudzeniowe. Dodatkowo w ramach badań laboratoryjnych postanowiono zweryfikować odporność izolatorów kompozytowych na działanie odchodów ptasich (degradacja powierzchni) oraz ich wpływ na wytrzymałość udarową.
PL
W artykule przedstawiono zagadnienia związane z napięciem udarowym wytrzymywanym izolatorów kompozytowych eksploatowanych w liniach średniego napięcia, na których zaobserwowano widoczne osady zabrudzeniowe. Dodatkowo w ramach badań laboratoryjnych postanowiono zweryfikować odporność izolatorów kompozytowych na działanie odchodów ptasich (degradacja powierzchni) oraz ich wpływ na wytrzymałość udarową.
EN
Some issues related to the surge impulse strength of MV line composite insulators with visible contamination deposits have been discussed in the article. Additionally, the resistance of composite insulators to bird droppings (surface degradation) together with the impact of these deposits on surge impulse strength have been verified by laboratory experiments.
PL
Najbardziej niebezpiecznymi uszkodzeniami mechanicznymi izolatorów są złamania izolatorów wsporczych i zerwania izolatorów odciągowych lub izolatorów wiszących. Rdzeń szkłoepoksydowy jest elementem, który zapewnia izolatorom kompozytowym dużą wytrzymałość na rozciąganie. Po 1998 roku w różnych krajach wykryto nowy rodzaj uszkodzeń, nazwany degradacyjnym pęknięciem prętów szkłoepoksydowych (decay-like fracture). Uszkodzenie osłony silikonowej izolatora kompozytowego jak i degradacja pręta szkłoepoksydowego mogą być procesami długotrwałymi. Proces uszkodzenia osłony izolatorów kompozytowych był obserwowany na stacji prób w Hucie Miedzi Głogów. Autorowi nie jest znany przypadek kruchego pęknięcia lub degradacyjnego pęknięcia pręta szkłoepoksydowego w Polsce. Kruche pęknięcia pręta szkłoepoksydowego izolatorów kompozytowych zostały wyeliminowane przez wprowadzenie włókien szklanych typu ECR.
EN
The most dangerous mechanical damage to insulators is the fracture of post insulators and the rupture of dead-end insulators or suspension insulators. The glass-fiber core is an element that provides composite insulators with high tensile strength. After 1998, a new type of damage was detected in various countries, called decay-like fracture. Damage to the silicone sheath of the composite insulator as well as degradation of the glass fiber core can be long-term processes. The process of damage to the sheath of composite insulators was observed at the Glogow pollution test station. The author is not aware of any case of brittle fracture or decay-like fracture of the glass fiber core in Poland. Brittle fracture of the glass fiber core of composite insulators have been eliminated by the introduction of ECR-type glass fibers.
EN
The paper presents the results of research on the influence of the electric charge deposited on composite insulators models on DC flashover voltage. The influence of the charge on the flashover voltage was observed on the level of 0-18%. That influence depended on the insulator position. There was no visible influence (occurrence of any regularity) of core and housing material on a flashover voltage.
PL
Przedstawiono wyniki badań wpływu ładunku elektrycznego zgromadzonego na modelach izolatorów kompozytowych na napięcie przeskoku przy narażaniu napięciem stałym. Wpływ ładunku na napięcie przeskoku był na poziomie 0-18%. Wpływ ten zależał od położenia izolatora. Nie było żadnego widocznego wpływu (wystąpienia jakichkolwiek regularności) materiału rdzenia i powłoki na napięcie przeskoku.
5
Content available remote Influence of the impulse voltage on the residual charge
EN
Results of measurements and simulations of the charge accumulated on the surface of composite insulator models after applying to them standard high voltage impulse (1.2/50 – positive polarity) are presented in the paper. Studies have shown that the residual charge deposited after applying the impulse with a positive polarity does not exceed 8nC and should not noticeably affect the flashover voltage tested models.
PL
W artykule przedstawiono wyniki badań ładunku zgromadzonego na powierzchni modelu izolatora kompozytowego po przyłożeniu do jednego z okuć standardowego udaru wysokonapięciowego (1.2/50) o biegunowości dodatniej. Badania wykazały, że wprowadzony w ten sposób ładunek resztkowy nie przekracza 8nC i nie powinien wpływać w zauważalny sposób na wartość napięcia przeskoku badanych modeli.
PL
Rosnąca stosowanie izolatorów kompozytowych wymaga doskonalenia kryteriów nie tyko ich odbioru, ale i weryfikacji i rozszerzenia dotychczasowych badań. Propozycją nowych badań opisanych w niniejszym artykule jest uwzględnienie działania siły cyklicznej na wytrzymałość izolatorów kompozytowych. Konieczność przeprowadzenia takich badań uwzględniono w nowej specyfikacji technicznej PSE S.A. „Kompozytowe izolatory wiszące do sieci 400 kV” (lipiec 2015 r.). Dalsze badania powinny uwzględniać nowe zjawiska i spełniać coraz ostrzejsze kryteria jakościowe, spełnienie jakich wpłynie istotnie na trwałość użytkowania tego typu izolatorów.
EN
Growing application of composite insulators needs improvement of not only the criteria of their technical acceptance but also verification and expanding current investigations. As a proposal of new investigations described in this article is going into direction of taking into consideration the resistance of composite insulators to cyclic loading. The necessity of conducting such investigations was taken into account in the new PSE S.A. technical specification „Hang-type composite insulators for a 400 kV network” (July, 2015). Further research should include new phenomena and conform to increasingly stringent quality criteria, meeting which can considerably influence durability of such insulators.
EN
This paper proposes a new compound mode composed of a composite insulator in series with glass insulators, designed to improve its electric field distribution based on its own capacitive electric field distribution characteristics. A three-dimensional electric field calculation model of a composite insulator in a transmission line was designed and employed to study the improved situation of the surface potential and the electric field distribution of a composite insulator, with a glass insulator installed in its high-voltage side at 110 kV.
PL
W artykule zaproponowano system połączenia izolatorów kompozytowych i szklanych. Obliczono numerycznie pole elektryczne modelu izolatora zainstalowanego w sieci 110 kV.
PL
Kompozytowe wsporcze izolatory stacyjne stosuje się w sieciach elektroenergetycznych na coraz większe prądy zwarcia. W badaniach znormalizowanych przewiduje się dla tych izolatorów tylko próby przy obciążeniu statycznym. Podczas przepływu prądów zwarcia na izolatory wsporcze oddziałują także zmienne siły zginające o dużych wartościach, zwykle o charakterze cyklicznym wahadłowym. W Instytucie Energetyki rozpoczęto prace nad wytrzymałością kompozytowych izolatorów wsporczych przy takich właśnie obciążeniach. Wstępny etap badań obejmował izolatory do sieci 110 kV. Wyznaczono charakterystyki zmęczeniowe i oszacowano wytrzymałość izolatorów przy obciążeniu zmiennym.
EN
Composite station post insulators are applied to electrical power grid where high surge currents can be periodically expected. Standard tests for these insulators base on application of static mechanical loads only while the composite station post insulators are subjected to variable cantilever forces of symmetrical cyclic character and high values being a result of impact of surge currents flow in to the grid. This type of variable loads has been applied to research works on mechanical strength of the insulators at the Institute of Power Engineering (IEn). Preliminary tests have been carried out for the insulators applied to 110 kV electrical power network. The fatigue characteristics are determined for these insulators to evaluate their mechanical strength at the variable loads.
EN
The composite insulators have been widely used on the power transmission lines. The faulty caused by manufacture techniques, quality defect or organic material degradation comes into being more and more. Measuring the composite insulator' corona pulse current flowing through the grounded wire is an excellent way to monitor the faulty insulator strings on ground. In this paper, the measurement system for detecting pulse current of composite insulator are set up. The wideband current transducer, extraction circuit of pulse current and the circuit of reference signal are designed and manufactured. Based on the experimental system set up in the laboratory, the characteristics of corona pulse are studied. The relationship between applied voltage and pulse current characteristics, the frequency and phase angle range of corona pulse are studied profoundly. Such work provides direction for on-line monitoring composite insulators by pulse current method.
PL
W artykule analizowano metody badania defektów izolatorów kompozytowych. Mierzono impulsowy prąd wyładowania przepływający przez uziemiony przewód. Przedstawiono układ pomiarowy tego prądu oraz przedstawiono wyniki eksperymentów. Analizowano związek między przyłożonym napięciem a prądem wyładowania, w tym właściwości częstotliwościowe i fazowe tego prądu.
PL
Opisano konstrukcję, wyniki badań oraz prób technologicznych izolatorów kompozytowych SN.
EN
The paper describes the structure, results of research and technological tests of MV composite insulators.
PL
Praca prezentuje wyniki badań emisji akustycznej (EA) w czasie zaciskania okuć na szkło-epoksydowych prętach nośnych wiszących izolatorów kompozytowych średniego napięcia produkcji krajowej. Uzupełniające badania ultradźwiękowe oraz mikroskopowe miały na celu porównanie parametrów akustycznych oraz strukturalnych tworzyw szklanoepoksydowych, wytworzonych różnymi metodami. Część prętów wykonana została metodą ciągłego formowania, natomiast pozostałe z zastosowaniem metody ciśnieniowej. Dokonano interpretacji różnic w charakterystyce akustycznej (EA) procesu zaciskania okuć dla obu rodzajów prętów. Stwierdzono, że zastosowane przy mocowaniu okuć ciśnienie miało większy wpływ na materiał prętów formowanych metodą ciągłą, który wykazywał niższą wytrzymałość mechaniczną.
EN
In this work acoustic emission, ultrasonic and microscopic methods of testing were applied to investigate the structure of composite rods, used as a component of medium-voltage electrical insulators. Influence of the technology of epoxy-glass material fabrication on quality parameters of the insulator rods was revealed. Investigation of the process of compressing of the fixing devices was carried out. Results of acoustic testing were compared with the effects of microscopic study. Effects of acoustic emission measurements are in good agreement with the results of microscopic and ultrasonic tests.
PL
W artykule przedstawiono rozwój konstrukcji i technologii izolatorów kompozytowych w ciągu ostatnich 30 lat. Opisano metody produkcji izolatorów i ich zalety oraz stosowane materiały do poszczególnych części izolatorów. Zwrócono uwagę na metody sterowania pola elektrycznego i zapewnienie szczelności osłony. Zestawiono kształty geometryczne i ich wpływ na własności izolatorów w warunkach zabrudzeniowych.
EN
The paper shows the advances in construction and technology of composite insulators during last 30 years. The production methods, their advantages and materials used for different insulator parts were described. Special attention was paid for electric field control and moisture penetration. The influence of different insulator shapes on pollution behavior was discussed.
PL
Przedstawiono analizę wyników prób zwarciowych kompozytowych izolatorów liniowych 110 kv. Omówiono wpływ łuku zwarcia na podstawowe parametry elektryczne i mechaniczne badanych izolatorów. Podano wyniki prób wytrzymałości elektrycznej przed i po działaniu łuku elektrycznego. Podano wyniki prób termomechanicznej i mechanicznej dla izolatorów poddanych próbie zwarciowej.
EN
Results of power arc tests carried out on composite insulators for 110 kV overhead lines are analyzed. The effect of arcing on the basic electrical and mechanical parameters of the tested insulators is examined. Results of pre- and post-arc electric strength tests as well as those of thermo mechanical and mechanical tests carried out on insulators subjected to the power arc test are presented.
PL
W NKP ds. Izolatorów systematycznie zmierza się do zapewnienia pełnej zgodności wymagań krajowych z międzynarodowymi (IEC) i europejskimi (EN). Zasadnicze trudności polegają na braku wystarczających środków finansowych. Obecnie przedstawiciel Polski bierze udział w pracach Grupy Roboczej IEC, która przygotowuje nową wersję publikacji IEC 815. W PKN trwają prace nad nowelizacją ustawy o normalizacji.
EN
Recent activity of Normalization Commission for Insulators is concentrated on ensuring the full agreement between national and international (as well as European) standards. Main problems are of financial nature. Now our representative takes part in works of the 36 WG11 Group, whose main duty is to elaborate a new version of the IEC 815 guide. Polish Normalization Communities is concentrated on elaboration of a new version of governmental normalization rule.
PL
W ostatnich latach opracowano konstrukcję izolatora hybrydowego, łączącego zalety tworzywa ceramicznego i materiałów organicznych. Izolatory takie przeznacza się do szczególnie trudnych warunków eksploatacji. Autorzy proponują konstrukcję izolatora hybrydowego z rdzeniem ceramicznym z tworzywa o znacznie większej wytrzymałości mechanicznej niż tradycyjna porcelana elektrotechniczna i z kloszami wykonanymi z elastomeru silikonowego. Przewiduje się, że izolatory te znajdują zastosowanie w trakcji elektrycznej 3 kv prądu stałego lub w aparaturze łączeniowej średniego napięcia.
EN
In order to join advantages of ceramic materials an idea of construction of hybrid insulator has been recently developed. These insulators are usually applied to extremely difficult operation conditions. In this paper, a new construction of a hybrid insulator is proposed. It consists of a ceramic rod and silicone rubber sheds. It is assumed that a ceramic material whose mechanical strength is much higher than that for traditional porcelain will be used. The insulators will be applied to DC electrical traction of 3 kv and to switchgears for middle level voltages.
PL
Na podstawie własnych obserwacji oraz dostępnych informacji przedstawiono obecne dziedziny stosowania izolatorów ceramicznych i kompozytowych. Przedstawiono opinie autorów dotyczące perspektyw zastosowania izolatorów ceramicznych i kompozytowych na rynku, na którym istnieje konkurencja. Analizując poszczególne rodzaje i grupy izolatorów, określono, w jakich urządzeniach będą stosowane głównie izolatory kompozytowe, a w jakich nadal - izolatory ceramiczne.
EN
Present fields of ceramic and composite insulators on the basic of authors' observations and accessible information are presented. The authors' opinion on the prospects of applications of ceramic and composite insulators in competition market is presented. There are discussed particular fields when composite insulators and ceramic ones will dominate.
PL
W artykule dokonano przeglądu problemów badawczych dotyczących izolatorów kompozytowych, stosowanych coraz powszechniej w elektroenergetyce. Przedstawiono aktualne problemy oceny specyficznych właściwości oraz jakości i trwałości izolatorów. Zwrócono również uwagę na potrzebę i problemy badań diagnostycznych izolatorów kompozytowych w eksploatacji.
EN
The review of research problem considering the evaluation of specific properties, quality and durability of the high voltage composite insulators has been presented. The diagnostic problems in service have also been pointed out.
first rewind previous Strona / 1 next fast forward last
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.