This paper presents simulation and laboratory test results of an implementation of an infinite control set model predictive control into a three-phase AC/DC converter. The connection between the converter and electric grid is made through an LCL filter, which is characterized by a better reduction of grid current distortions and smaller (cheaper) components in comparison to an L-type filter. On the other hand, this type of filter can cause strong resonance at specific current harmonics, which is efficiently suppressed by the control strategy focusing on the strict control input filter capacitors voltage vector. The presented method links the benefits of using linear control methods based on a space vector modulator and the nonlinear ones, which result in excellent control performance in a steady state as well as in a transient state.