The importance of the problem of electrical power quality arises from the economical reasons. The electrical power quality is expressed by the set of coefficients like the total harmonic distortion, the total power factor, the power displacement factor. The normalised values of these factors are very demanding. From the analyses carried out by many scientific centres it is concluded that only the active power electronics systems can meet these demands. The presented problem is especially concerned with rectification systems. The classical diode and thyristor rectifier systems, widely applied in Poland, have the current total harmonics distortion ratio about 30% while the planned normalised value is about 5 %. It makes the problem of improłing of the electrical power quality of the rectifier's systems be common and important
PL
Istotność problemu jakości mocy elektrycznej wynika z przyczyn natury ekonomicznej. Jakość mocy elektrycznej wyrażana jest poprzez zespól współczynników takich jak współczynnik THD, współczynnik mocy, współczynnik mocy przesunięcia. Znormalizowane wartości tych współczynników są bardzo wymagające. Analizy przeprowadzone w wielu jednostkach naukowych na świecie wykazały, że jedynie systemy energoelektroniczne pozwalaj ą spełnić te wymagania. Omawiany problem jest szczególnie związany z układami prostowniczymi. Klasyczne prostowniki diodowe i tyrystorowe, szeroko stosowane w Polsce, posiadaj ą współczynnik THD wynoszący około 30% podczas gdy planowane normy wymagają aby wartość tego współczynnika była mniejsza od 5%. Powoduje to, że problem jakości mocy elektrycznej pobieranej przez prostowniki jest ważny i aktualny.
EN
The subject of this paper is theoretical and simulation investigation of modified diode rectifier with improved power factor assembled according to proposition presented in [l], The modified diode rectifier with additional power electronic valves used for modelling of multilevel voltage at the input of the diode rectifier is analysed. The mathematical model of the analysed rectifier system is presented. The control characteristics of the rectifier system are derived, constrains involved by the multilevel voltage generation scheme are pointed. The main conclusion derived from the perfomed analysis is that the modified rectifier system allow to obtain significant reduction of the THD(i) factor but only in the case of the nominal load.
PL
Tematem prezentowanej pracy są badania teoretyczne i symulacyjne prostownika o poprawionym współczynniku mocy, zrealizowanego według pomysłu przedstawionego w pracy |1]. W pracy przedstawiono szczegółową analizę zmodyfikowanego układu trójfazowego mostka diodowego, w którym zastosowano dodatkowe łączniki do kształtowania przebiegu czasowego napięcia na zaciskach wejściowych mostka diodowego. Zaprezentowany został model matematyczny układu oraz wyniki badań symulacyjnych. Wyprowadzono charakterystyki sterowania układu i wynikające z metody kształtowania wejściowego napięcia schodkowego na zaciskach mostka diodowego ograniczenia zakresu sterowania. Wykazano, że układ umożliwia uzyskanie istotnego zmniejszenia THD(i), jednakże tylko w warunkach obciążenia znamionowego.