The paper presents the two-dimensional, field-circuit model of a high power synchronous generator verified by measurements. The model enables determining the waveforms of electromagnetic quantities in steady and transient states. Verification of the model was based on comparison of the measured and calculated waveforms after a disturbance in the voltage regulation system of a TWW-200-2 generator operating in Połaniec Power Plant. There are also presented the field methods for determining electromagnetic parameters (synchronous reactances and time constants) when using the distributions of static and quasi-static, magnetic and electromagnetic fields calculated by the finite element method (FEM). The set of these parameters was used as the starting parameters of the optimization algorithm for estimation of electromagnetic parameters of the synchronous generator circuit model. The dynamic waveforms under the generator load conditions calculated by the finite element method are the basis of parameter estimation. The parameter estimation of the generator model was performed with the use of the least squares method.