EN
The assessment of voltage disturbing emission sources still lacks adequate models for customer side incorporating mixed loads and distributed power generation. The paper proposes a solution for this challenging task. It includes the determination of topology and parameters of equivalent circuits representing customers’ installations with local power sources in three- and four-wire networks. The equivalent circuits are developed on the basis of two-staged transformation, meet requirements of IEC 61000-4-30 and can be used for the on-line assessment of the emission sources of linear voltage disturbances.
PL
W artykule zaproponowano rozwiązanie problemu konkurujących zadań w sieci zawierającej różne obciążenia I rozproszone generatiry. Określono topologię I parametry obwodów zastępczych reprezentujących instalacje klientów w sieci trzy- I czteroprzewodowej. Schematy zastępcze okręslono na bazie dwustopniowej transformacji z uwzględnieniem normy IEC 61000-4-30. Pozwoliło to na okręślanie on-line źródeł emisji zakłóceń.