EN
A polyvinyl anti-corrosion coating system used to protect the lightning masts installed at a 400 kV substation showed significant damage after three years of operation. Field tests (measurements of thickness, adhesion, continuity using the low-voltage method, and the appearance of the coatings was assessed using a field microscope) and laboratory tests (infrared spectroscopy, examination of the morphology and elemental composition of the coatings under a scanning microscope with an EDX attachment) were carried out on collected samples. Degradation of the organic part of the protection was observed. Local exposure of the coatings to high temperatures was likely the cause of the damage.
PL
Poliwinylowy powłokowy system antykorozyjny zastosowany na słupach odgromowych stacji 400 kV uległ znacznemu zniszczeniu po trzech latach eksploatacji. Wykonano badania polowe (pomiary grubości, przyczepności, szczelności metodą niskonapięciową, oceniono wygląd powłok przy użyciu mikroskopu polowego) oraz badania laboratoryjne na pobranych próbkach (spektroskopię w podczerwieni, badania morfologii i składu pierwiastkowego powłok pod mikroskopem skaningowym z przystawką EDX). Stwierdzono degradację organicznej części zabezpieczeń. Przyczyną zniszczeń było prawdopodobnie miejscowe oddziaływanie na powłoki wysokiej temperatury.
first rewind previous Strona / 1 next fast forward last
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.