This paper presents and discusses investigated results of the performance of the newly developed ground fault protection using Hall sensor under real short-circuits to the ground in 6kV and 20kV networks of an opencast mine. Inspections were carried out during both metallic and high resistive faults in isolated and compensated mine networks where conventional protections failed in operation.
PL
W artykule przedstawiono i przeanalizowano wyniki badań zachowania się nowego czułego zabezpieczenia ziemnozwarciowego z czujnikiem Halla w warunkach rzeczywistych zwarć doziemnych w sieci górniczej 6 kV I 20 kV.
2
Dostęp do pełnego tekstu na zewnętrznej witrynie WWW
This paper presents results obtained from a series of investigations into efficient applicability of existing electric diagnosis systems applied to hermetic dc contactors under abnormal conditions of operation of a contact system. The study focuses on the influence of factors such as gas composition, pressure and temperature of a protective gaseous medium and contact material. Furthermore, the ambient temperature and chamber tightness are also considered from the point of view of reliable detection of switch malfunction at contact opening. The study reveals the need for development of a new structure of electric diagnosis systems of a much higher efficiency that are applicable to Hermetic Devices.
PL
Artykuł przedstawia rezultaty badań skuteczności stosowanych metod diagnozy jakości hermetycznych łączników DC w nietypowych warunkach pracy. Badania koncentrowały się na takich parametrach jak: skład gazu, ciśnienie i temperatura gazowego medium ochronnego i styków. Dodatkowo, badano wpływ temperatury otoczenia i naprężeń. Badania wykazały potrzebę rozwoju nowych metod diagnostycznych.
This paper presents and discusses results of the study of the arc-to-glow transformation phenomenon at contact opening, under dc inductive loads of low power (<10 J) and low voltage (< 250 V). The mathematical model describing consecutive stages of the arc-to-glow dynamics is elaborated, while heat transportation in contacts is considered using the ANSYS program. The proportion in duration of arcing and glowing is investigated with respect to circuit parameters, contact material properties, gas quenching medium and its pressure. The transition phenomenon is also investigated by means of fast photography and emission spectroscopy. On the basis of both theoretical and investigated results the conclusions about the possibility to control the arc-to-glow transformation for practical use in electrical control switching devices are formulated.
PL
W artykule przedstawiono wyniki analiz teoretycznych oraz badań eksperymentalnych zjawiska transformacji łuku elektrycznego w wyładowanie jarzeniowe podczas przerywania prądu stałego malej mocy (< 10 J) i niskiego napięcia (< 250 V) o charakterze indukcyjnym. Procesy termiczne w zestyku i stykach analizowano przy wykorzystaniu programu ANSYS, zaś w celu oceny wpływu poszczególnych zjawisk fizycznych na dynamikę transformacji opracowano odpowiedni model matematyczny. Czasy trwania luku elektrycznego i wyładowania jarzeniowego pomierzono w zależności od parametrów indukcyjnego obwodu łączeniowego, parametrów fizycznych i chemicznych materiału stykowego oraz rodzaju i ciśnienia stosowanego medium gaszącego. Obserwacje zjawisk wykonano również przy wykorzystaniu szybkiej fotorejestracji i fotospektroskopii. Na podstawie uzyskanych wyników sformułowano wnioski odnośnie do praktycznej możliwości sterowania przejściem łączeniowego łuku elektrycznego w wyładowanie jarzeniowe w stykowej elektrycznej aparaturze łączeniowej.
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.