Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników

Znaleziono wyników: 1

Liczba wyników na stronie
first rewind previous Strona / 1 next fast forward last
Wyniki wyszukiwania
help Sortuj według:

help Ogranicz wyniki do:
first rewind previous Strona / 1 next fast forward last
EN
The basic measure of the power system defence against sudden imbalance due to generation deficit is the Automatic Frequency Load Shedding (AFLS). Every transmission system operator (TSO), to whom the NC ER/2017 code applies, shall be obliged to use in their defence plan the AFLS automation that meets the guidelines set out there. In the simulation tests carried out using the DAKAR program, the AFLS was modelled in accordance with the guidelines of NC ER/2017 and the current requirements of the Transmission Network Code (IRiESP). The selected area concerned the northwestern part of the National Power System with a large imbalance and a sudden decrease in frequency. Advantages of NC ER/2017 entries have been pointed out.
PL
W planie obrony systemu elektroenergetycznego przed nagłym niezbilansowaniem, związanym z deficytem mocy generacyjnej, jako podstawowy środek obrony stosuje się automatykę samoczynnego częstotliwościowego odciążania (SCO). Każdy z opera- torów systemów przesyłowych (OSP), którego dotyczy NC ER/2017, jest zobowiązany do stosowania w swoim planie obrony automatyki SCO spełniającej podane w kodeksie wytyczne. W badaniach symulacyjnych, przeprowadzonych za pomocą programu DAKAR, zamodelowano automatykę SCO zgodnie z wytycznymi NC ER/2017 oraz dotychczasowymi wymogami Instrukcji Ruchu i Eksploatacji Sieci Przesyłowej (IRiESP). Wydzielany obszar dotyczył północno-zachodniej części KSE z dużym niezbilansowaniem i nagłym spadkiem częstotliwości. Wskazano zalety zapisów NC ER/2017.
first rewind previous Strona / 1 next fast forward last
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.