EN
The paper shows how fixed-parameters reactive compensators in four-wire systems with a nonsinusoidal voltage can be converted into controlled-parameters compensators. Such compensators can serve as adaptive balancing compensators of reactive power of unbalanced loads. Thyristor switch inductors (TSIs) are used for such conversion. The fixed-parameters balancing reactive compensators are synthesized using the Currents’ Physical Components (CPC) – based power theory. The adaptive compensator is composed of two sub-compensators, one in the structure and the other in the structure. The method is illustrated with a numerical example and results of computer modeling of the load with a fixed-parameters and with an adaptive compensator.
PL
Artykuł pokazuje jak równoważący kompensator reaktancyjny prądu biernego, o sta łych parametrach, w systemach cztero- przewodowych, może być przekształcony w kompensator o parametrach kontrolowalnych. Kompensator taki może być użyty jako kompensator adaptacyjny. Przekształcenie takie umożliwiają włączane tyrystorami induktory (TSI). Parametry równowa żącego kompensator prądu biernego mogą być obliczone z pomocą teorii mocy opartej na Składowych Fizycznych Prądu (CPC). Kompensator jest zbudowany z dwóch sub-kompensatorów, z którch jeden ma strukturę X, a drugi strukturę Y. Przedstawiona w artykule metoda syntezy jest ilustrowana przykładami liczbowymi i rezultatami kompensacji.
EN
The CPC-based power theory (PT) provides fundamentals for the development of the reactive compensators needed for the improvement of the effectiveness of the energy transfer. It also provides fundamentals for the development of algorithms for control of switching compensators and hybrid compensators that serve the same purpose. These fundamentals have been developed, along with the CPC, step-by-step, with partial results published in Polish, German, English and American journals and in conference proceedings, often not reported on the main databases and consequently, difficult to be found. This Review provides a draft of these CPC-based fundamentals of compensation with references to more detailed results.
PL
Teoria mocy obwodów i systemów elektrycznych, oparta na koncepcji Składowych Fizycznych Prądów, tworzy podstawę teoretyczną syntezy kompensatorów potrzebnych do poprawy skuteczności przenoszenia energii. Dotyczy to także podstaw konstrukcji algorytmów sterowania kompensatorów kluczujących oraz hybrydowych. Metody kompensacji, oparte na teorii mocy CPC, były rozwijane stopniowo, z częściowymi wynikami publikowanymi w polskich, niemieckich, angielskich oraz amerykańskich czasopismach i materiałach konferencyjnych, często nie notowanych w głównych indeksach i trudnych do odnalezienia. Przegląd ten zestawia wynikające z teorii mocy CPC metody syntezy kompensatorów reaktancyjnych i algorytmy sterowania kompensatorów kluczujących, ze wskazaniem źródeł bardziej szczegółowych wyników.
EN
The CPC-based power theory (PT) of electrical circuits and systems provides an interpretation of the energy transfer-related physical phenomena in such systems and fundamentals for their compensation. It has been developed, step-by-step, with partial results published in Polish, German, English and American journals and in conference proceedings, often not reported on the main databases and consequently, difficult to be found. Its development was a reaction for the lack of progress in long-lasting attempts aimed at explanation of the energy transfer-related physical phenomena and the lack of fundamentals for compensation in electrical systems with nonsinusoidal voltages. This Review provides a draft of the whole CPC concept with references to more detailed results and a concise historical background and critical comments on other power theories.
PL
Teoria mocy obwodów i systemów elektrycznych, oparta na koncepcji Składowych Fizycznych Prądów, tworzy podstawę teoretyczną dla interpretacji zjawisk fizycznych towarzyszących przesyłowi energii w takich układach i ich kompensacji. Była ona rozwijana stopniowo, z cząstkowymi wynikami publikowanymi w czasopismach polskich, niemieckich, angielskich i amerykańskich oraz w materiałach konferencyjnych, często trudnych do odnalezienia. Rozwój CPC był odpowiedzią na brak postępu w badanich nad teorią mocy i na brak podstaw kompensacji w układach z napięciami niesinusoidalnymi. Przegląd ten jest skrótem CPC, z odnośnikami do bardziej szczegółowych wyników oraz z tłem historycznym i krytycznymi uwagami dotyczącymi wyników innych teorii mocy.
EN
The paper provides the Currents’ Physical Components (CPC)-based fundamentals for reactive balancing of unbalanced loads supplied by a nonsinusoidal voltage in four-wire systems, meaning with a neutral conductor. The whole compensation of the unbalanced and reactive currents in such conditions requires reactive compensators of high complexity, i.e., built of a high number of reactive devices. This complexity can be reduced on the condition that the objective of a whole compensation is abandoned for a goal of only minimization of the supply current three-phase rms value. The paper presents a method of minimization of this three-phase rms value of the supply current by a compensator composed of branches, that have no more than two reactive devices, meaning an inductor and a capacitor.
PL
Artykuł przedstawia podstawy, oparte na teorii Składowych Fizycznych Prądów (Ang. CPC), reaktancyjnego równoważenia odbiorników niezrównoważonych, zasilanych napięciem niesinusoidalnym w układach czteroprzewodowych, to jest z przewodnikiem zerowym. Całkowita kompensacja prądu niezrównoważenia i prądu biernego wymaga w takich warunkach kompensatorów o wysokiej złożoności, to jest o dużej liczbie elementów reaktancyjnych. Złożoność tę można obniżyć przez rezygnację z całkowitej kompensacji na rzecz jedynie minimalizacji trójfazowej wartości skutecznej prądu zasilania. Artykuł przedstawia metodę takiej minimalizacji z pomocą kompensatora zbudowanego z gałęzi mających nie więcej niż dwa elementy reaktancyjne, to jest cewkę indukcyjną i kondensator.
EN
Energy flow related phenomena in three-phase unbalanced, linear, time-invariant (LTI) loads, supplied with asymmetrical, but sinusoidal voltage, in three-wire systems, are investigated in the paper. It is demonstrated that the load current can be decomposed into Currents’ Physical Components (CPC), associated with distinctive physical phenomena in the load. It is also shown how the CPC can be expressed in terms of the supply voltage and equivalent parameters of the load. An equivalent circuit of LTI loads at asymmetrical, but sinusoidal supply voltage is presented as well. This decomposition provides solid fundamentals for defining powers of such loads.
PL
Artykuł przedstawia wyniki badań nad zjawiskami energetycznymi w liniowych, czasowo-niezmienniczych (LTI) odbiornikach niezrównoważonych, zasilanych niesymetrycznym, lecz sinusoidalnym napięciem w obwodach trójprzewodowych. Pokazano, że prąd takich odbiorników może być rozłożony na Składowe Fizyczne, jednoznacznie stowarzyszone z określonymi zjawiskami fizycznymi. Pokazano także, że prądy te mogą być określone poprzez napięcie zasilania i parametry równoważne odbiornika. Przedstawiono także obwód równoważny niezrównoważonych odbiorników LTI, zasilanych niesymmetrycznym, lecz sinusoidalnym napięciem. Rozkład ten tworzy solidne podstawy dla definicji mocy takich odbiorników.
EN
Energy flow related phenomena in three-phase systems with neutral conductor and unbalanced, linear, time-invariant (LTI) loads, supplied with nonsinusoidal, but symmetrical voltage are investigated in the paper. It is demonstrated that the load current can be decomposed into Currents’ Physical Components (CPC), associated with distinctive physical phenomena in the load. It is also shown how the CPC can be expressed in terms of the supply voltage and equivalent parameters of the load. This decomposition provides solid fundamentals for defining powers of such loads.
PL
Artykuł przedstawia wyniki badań nad zjawiskami energetycznymi w liniowych, czasowo-niezmienniczych (LTI) odbiornikach niezrównoważonych, zasilanych niesinusoidalnym lecz symetrycznym napięciem w układach trójfazowych z przewodnikiem neutralnym. Pokazano, że prąd zasilania takich odbiorników może być rozłożony na Składowe Fizyczne, jednoznacznie stowarzyszone z określonymi zjawiskami fizycznymi. Pokazano także, że prądy te mogą być określone poprzez napięcie zasilania i parametry równoważne odbiornika. Rozkład ten tworzy solidne podstawy dla definicji mocy takich odbiorników.