Investigation of the magnetic field distribution on the surface of AMF contacts

Treść / Zawartość
Identyfikatory
Warianty tytułu
PL
Badania rozkładu pola magnetycznego na powierzchni styków AMF
Języki publikacji
EN
Abstrakty
EN
The axial magnetic field (AMF) distribution on the contact surface plays an important role in short circuit current interruption. To minimize erosion of the contact the AMF should be uniformly distributed over the contact plates. During theoretical analysis of bipolar contacts, the design of the contact coil and the slots made in the contact’s plate, as well as the orientation of the steady contact relative to the moving contact were taken into account. The FLUX 3-D computer program was used for the calculation of the AMF and the results were compared and analyzed. To investigate the distribution of arc spots on the contact plate surface experiments were conducted in a dismountable vacuum chamber during a 15 kA short circuit current interruption.
PL
Rozkład osiowego pola magnetycznego na powierzchni styków komór próżniowych odgrywa decydującą rolę w ograniczaniu erozji styków podczas wyłączania prądu zwarciowego. Ograniczenie erozji styków możliwe jest przez równomierny rozkład osiowego pola magnetycznego na całej powierzchni styku. Z tego względu, w projektowaniu styków, należy stosować metody obliczeniowe do sprawdzenia składowej osiowej rozkładu pola magnetycznego. W artykule podano wynik analizy rozkładu składowej osiowej pola magnetycznego dla styku bipolarnego z nacięciami ukośnymi i z nacięciami o kształcie łuku. Do analizy stosowano program komputerowy FLUX 3D. Wykonano również badania rozkładu strumienia łuku dyfuzyjnego w rozbieralnej komorze próżniowej podczas wyłączania prądu zwarciowego o wartości 15 kA.
Rocznik
Tom
Strony
7--13
Opis fizyczny
Bibliogr. 10 poz.
Twórcy
autor
  • Electrotechnical Institute, M. Pożaryskiego 28, 04-703 Warsaw, Poland
  • Electrotechnical Institute, M. Pożaryskiego 28, 04-703 Warsaw, Poland
autor
  • Electrotechnical Institute, M. Pożaryskiego 28, 04-703 Warsaw, Poland
autor
  • Electrotechnical Institute, M. Pożaryskiego 28, 04-703 Warsaw, Poland
Bibliografia
  • 1. Homma M., Somei H., Niva Y., Yokokura K. and Ohsima I.: Physical and theoretical aspects of a new vacuum arc control technology – self arc diffusion by electrode, SADE. Proc. 18thISDEIVE, Eindhoven, The Netherlands, pp. 415–422, 1998.
  • 2 Kulkarni S., Rajan S., Andrews L., Rajhans R. and Thomas J.: Influence of uniformity of the axial magnetic field in a vacuum interrupter on the performance of the contacts. XXIII-rd Int. Symp. on Discharges in Vacuum, Bucharest, 2008.
  • 3. Lee J. C., Cho S. H., Lee H. G., Choi M. J., Kwon J. R. and Kim Y. J.: 3-D numerical analysis of diffuse vacuum arc with an axial magnetic field. XXIII-rd Int. Symp. on Discharges in Vacuum, Bucharest, 2008.
  • 4. Shi Z., Song X., Liu Z., Dong H. and Wang L.: The influence of axial magnetic field distribution on high–current vacuum arc. IEEE Transactions on Plasma Science, vol. 37, No. 8, August 2009.
  • 5. Zhang X., Wang X., Guan Q., Li M.: A new axial magnetic field contact there – quarters of coil for high-voltage vacuum interrupter and its properties. XXVIIth Int. Symp. on Discharges and Electrical Insulation in Vacuum, Suzhou, 2016.
  • 6. Ma H., Zhang Z., Ferrari S., Wang J., Geng Y. and Liu Z.: Method to determine rotation velocity of constricted vacuum arcs driven by transverse magnetic field. XXVIIth Int. Symp. on Discharges and Electrical Insulation in Vacuum, Suzhou, 2016.
  • 7. Zhang Y., Shi Z., Wang J., Q., Jia S., Wang L.: Simulation on the residual axial magnetic field in vacuum dc interruption based on artificial current zero. XXVIIth Int. Symp. on Discharges and Electrical Insulation in Vacuum, Suzhou, 2016.
  • 8. Kwiatkowski B., Kwater T., Koziorowska A.: Influence of the distribution component of the magnetic induction vector on rupturing capacity of vacuum switches. Discrete and Continuous Dynamical Systems Supplement , www.aimSciences.org, pp. 913–921, 2011.
  • 9. Krasuski K., Sibilski H., Dzierżyński A.: Badania układów stykowych w rozbieralnej komorze próżniowej. Materiały konferencyjne „Modelowanie, Symulacja i Zastosowanie w Technice”, Kościelisko, 2012.
  • 10. Krasuski K., Sibilski H., Dzierżyński A.: Badania układów stykowych w rozbieralnej komorze próżniowej, Wiadomości Elektrotechniczne, pp. 55–58, 12 2012.