Calculations of electromechanical eigenvalues based on instantaneous power waveforms

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Obliczenia elektromechanicznych wartości własnych na podstawie przebiegów mocy chwilowej
Języki publikacji
EN
Abstrakty
EN
The paper presents the results of calculations of the eigenvalues (associated with electromechanical phenomena) of the Polish National Power System model on the basis of analysis of the simulated and measured instantaneous power disturbance waveforms of generating units in Łaziska Power Plant. The method for calculations consists in approximation of instantaneous power swing waveforms in particular generating units with use of the waveforms being a superposition of the modal components associated with the searched eigenvalues and their participation factors.
PL
W artykule przedstawiono wyniki obliczeń wartości własnych (związanych ze zjawiskami elektromechanicznymi) modelu Krajowego Systemu Elektroenergetycznego na podstawie analizy symulacyjnych i pomiarowych przebiegów mocy chwilowej zespołów wytwórczych w elektrowni Łaziska. Wykorzystana metoda obliczeń polega na aproksymacji przebiegów odchyłek mocy chwilowej za pomocą przebiegów stanowiących superpozycję składowych modalnych związanych z poszukiwanymi wartościami własnymi i ich czynnikami udziału.
Rocznik
Strony
214--217
Opis fizyczny
Bibliogr. 10 poz., il., tab., wykr.
Twórcy
autor
  • Politechnika Śląska, Wydział Elektryczny, Instytut Elektrotechniki i Informatyki ul. Akademicka 10, 44-100 Gliwice
autor
  • Politechnika Śląska, Wydział Elektryczny, Instytut Elektrotechniki i Informatyki ul. Akademicka 10, 44-100 Gliwice
Bibliografia
  • [1] Paszek S., Nocoń A.: The method for determining angular stability factors based on power waveforms. AT&P Journal Plus2, Power System Modeling and Control, Bratislava, Slovak Republic 2008, pp. 71-74.
  • [2] Cetinkaya H.B. Ozturk S., Alboyaci B.: Eigenvalues Obtained with Two Simulation Packages (SIMPOW and PSAT) and Effects of Machine Parameters on Eigenvalues. Electrotechnical Conference, 2004. MELECON 2004. Proceedings of the 12th IEEE Mediterranean, Vol. 3, pp. 943-946.
  • [3] Saitoh H., Miura K., Ishioka O., Sato H., Toyoda J.: On-line modal analysis based on synchronized measurement technology. Power System Technology, 2002. Proceedings. PowerCon 2002. International Conference on, vol. 2, pp. 817 – 822.
  • [4] Kudła J., Paszek S.: Reduced-order transfer function in Power System (in Polish). 18-th International Conference on Fundamentals of Electrotechnics and Circuit Theory, SPETO’95,vol. 2, pp. 299-304.
  • [5] Pruski P., Paszek S.: Calculations of electromechanical eigenvalues based on simulation and measurement instantaneous power waveforms of generating units (in Polish). Zeszyty Naukowe Politechniki Śląskiej „Elektryka”, Gliwice 2012, zeszyt 2, rok LVIII, s. 71-88.
  • [6] Paszek S., Pruski P.: Assessment of the power system angular stability based on analysis of selected disturbance states. Acta Energetica, nr 02/2011, pp. 44-53.
  • [7] Majka Ł., Paszek S.: Use of hybrid algorithm for estimation of generating unit mathematical model parameters (in Polish). Przegląd Elektrotechniczny 2010, R. 86, nr 8, s. 70-76.
  • [8] Paszek S.: Selected methods for assessment and improvement of power system angular stability. Wydawnictwo Politechniki Śląskiej, Gliwice 2012.
  • [9] Power Technologies, a Divi s ion of S&W Consul - tants Inc . : Program PSS/E Application Guide. Siemens Power Technologies Inc., 2002.
  • [10] Oppenheim A. V., Schafer R. W.: Discrete-time signal processing. 2nd Edition. Prentice Hall. Upper Saddle River 1999.