An algorithm for transformer hot spot temperature determining

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Algorytm do wyznaczania temperatury hot spotu transformatora
Języki publikacji
EN
Abstrakty
EN
This paper presents an algorithm for the winding temperature change estimation and the hot spot temperature determining of an oil filled power transformer. The proposed algorithm is based on the functional relation between the change of winding resistance and the measured oil temperature. The temperature changes approximation is based on the method of least squares. The proposed method is applied in the software for a field test instrument and verified by the field experiments.
PL
W artykule przedstawiono algorytm służący do szacowania zmian temperatury uzwojeń oraz wyznaczania temperatury najgorętszego miejsca (ang. hot spot) w transformatorze wypełnionym olejem. Proponowany algorytm oparty jest na funkcjonalnej zależności pomiędzy zmianą rezystancji uzwojenia a mierzoną temperaturą oleju. Aproksymacja zmiany temperatury bazuje na metodzie najmniejszych kwadratów. Zaproponowana metoda stosowana jest w oprogramowaniu przyrządu testującego i zweryfikowana została eksperymentalnie.
Rocznik
Strony
141--145
Opis fizyczny
Bibliogr. 20 poz., tab., wykr.
Twórcy
autor
  • University of East Sarajevo Faculty of Electrical engineering, Vuka Karadzica 30, 71123 East Sarajevo, Bosnia and Herzegovina
autor
  • University of East Sarajevo Faculty of Electrical engineering, Vuka Karadzica 30, 71123 East Sarajevo, Bosnia and Herzegovina
autor
  • University of Banja Luka, Faculty of Electrical Engineering, Patre 5, 78000 Banja Luka, Bosnia and Herzegovina
Bibliografia
  • [1] Perez J., Fundamental principles of transformer thermal loading and protection, Conference for Protective Relay Engineers, TX. USA, March 29-April 1, (2010), 1-14
  • [2] IEC Std 60076-2, Power Transformers, Part 2: Temperature rise for liquid-immersed transformers, (2011)
  • [3] IEC Std 60076-7, Power Transformers, Part 7: Loading guide for oil-immersed power transformers, (2009)
  • [4] IEEE Std C57.12.90, Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers, (2010)
  • [5] IEEE Std 1538-2000, „IEEE Guide for Determination of Maximum Winding Temperature Rise in Liquid-Filled Transformers,” (2000)
  • [6] Pierce L.W., An investigation of the thermal performance of an oil filled transformer winding, IEEE T. Power Deliver, 7 (1992), 1347-1358
  • [7] teNyenhuis E.G., Girgis R.S., Mechler G.F., Zhou G., Calculation of core hot-spot temperature in power and distribution transformers, IEEE T. Power Deliver, 17 (2002), 991-995
  • [8] Douglas D., Lawrence C., Templeton J., Factory Overload Testing of a Large Power Transformer, IEEE T Power Ap. Syst., 104 (1985), 2492-2500
  • [9] Miller S.J., The Method of Least Squares,. Math Brown, Providence: Brown University, (2006),1-7
  • [10] IEEE Std 62-1995. IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus-Part 1, (2005)
  • [11] Radosavljevic R.Lj., Popovic A., Milosavljevic V., Damjanovic M., Temperature Measurement of Primary Windings of Transformers in the Hydro-Electric Power Plant “Djerdap 1“ rated 380 MVA, 2x15,75 kV/420 kV, d5/d5/YN, OFWF, under Load after 30 years operation, CIGRE, Paris, (2004), A2-106, 1-8
  • [12] Sidi A., Interpolation at equidistant points by a sum of exponential functions, J. Approx. Theor. 34 (1982), 194-210
  • [13] IEC Std 60076-1, Power Transformers, Part 1: Temperature rise for liquid-immersed transformers, (2011), 87-89
  • [14] Aubin J., Langhame Y., Efect of oil viscosity on transformer loading capability at low ambient temperature, IEEE T. Power Deliver., 7 (1992), 516-524
  • [15] Susa D., Nordman H., A Simple Model for Calculating Transformer Hot-Spot Temperature, IEEE T. Power Deliver., 24 (2009), 1257-1265
  • [16] Pradhan M.K., Ramu T.S., Estimation of the Hottest Spot Temperature (HST) in Power Transformers Considering Thermal Inhomogeneity of the Windings, IEEE T. Power Deliver, 19 (2004), 1704-1712 [17] Taghikhani M.A., Power Transformer Winding Thermal Analysis Considering Load Conditions and Type of Oil, Int J. Mat. and Mech. Eng, 1 (2012), 109-113
  • [18] Kweon D.J., Koo K.S., Woo J.W., Kwak J.S., A Study on the Hot Spot Temperature in 154kV Power Transformers, J. Elec. Eng. Tech, 7 (2012), 312-319
  • [19] Radakovic Z., Feser K., A new method for the calculation of the hot-spot temperature in power transformers with onan cooling, IEEE T. Power Deliver, 18 (2003), 1284-1292
  • [20] Roizman O., Davydov V., Temperature rise test, IEEE TCM; Miami, FL, (2009), 1-25