Działanie przekaźnika ziemnozwarciowego na podstacji przychodzącej Feedera 15 Zwarcie w podstacji 14 Plaju media PT. Rafineria Pertamina (Persero) III Plaju – Sungai Gerong
Języki publikacji
Abstrakty
The distribution network of PT. Pertamina (Persero) Refinery unit 3 Plaju - Sungai Gerong uses an underground cable type of conductor, where most of the switchbreakers and relays at substation 14 Plaju are still analog. one of which is the ground fault relay (GFR) on feeder A incoming substation 15 on substation 14 Plaju, for a long time the relay has not been reset, causing a tendency to reduce the sensitivity level of the relay in securing the system when a fault occurs (short circuit). ), to overcome this, it is necessary to evaluate and reset the fault relay to ground. Evaluation is done by calculating the fault current of 3 phase, 2 phase, and 1 phase to ground to determine the magnitude of the fault current in the feeder A delivery line and compare it to determine the ideal ground fault relay (GFR) setting. Based on the calculation, ideally setting the ground fault relay (GFR) for incoming substation 15 breaker at substation 14 Plaju on feeder A side 12 kV forIsetprimary 32.244 Aand Isesecondary t is0.107 A with t (time) 0.298 s while on the feeder side 6.6 kV, namely the primary Iset of 25.795 A and the secondary Iset of 0.081 A with t (time) of 0.308 s.
Sieć dystrybucyjna PT. Pertamina (Persero) Jednostka rafineryjna 3 Plaju - Sungai Gerong wykorzystuje przewód typu podziemnego kabla, w którym większość wyłączników i przekaźników w podstacji 14 Plaju jest nadal analogowa. jednym z nich jest przekaźnik ziemnozwarciowy (GFR) na linii zasilającej Podstacja przychodząca 15 na podstacji 14 Plaju, przez długi czas przekaźnik nie był resetowany, co powoduje tendencję do zmniejszania poziomu czułości przekaźnika w zabezpieczaniu systemu, gdy wystąpi usterka (zwarcie). ), aby temu zaradzić, konieczne jest oszacowanie i zresetowanie przekaźnika błędu do masy. Oceny dokonuje się poprzez obliczenie prądu zwarciowego 3-fazowego, 2-fazowego i 1- fazowego do ziemi w celu określenia wielkości prądu zwarciowego w linii zasilającej A i porównanie go w celu określenia idealnego ustawienia przekaźnika zwarcia doziemnego (GFR). W oparciu o obliczenia, najlepiej ustawić przekaźnik ziemnozwarciowy (GFR) dla przychodzącego wyłącznika podstacji 15 w podstacji 14 Plaju po stronie linii A 12 kV dla Isetprimary 32,244 Ai Isesecondary t jest 0,107 A z t (czas) 0,298 s po stronie linii 6,6 kV, czyli Iset pierwotny 25,795 A i Iset wtórny 0,081 A z t (czas) 0,308 s.
Słowa kluczowe
Wydawca
Czasopismo
Rocznik
Tom
Strony
72--75
Opis fizyczny
Bibliogr. 10 poz., rys., tab.
Twórcy
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
autor
- Department of Electrical Engineering, Faculty of Engineering, Muhammadiyah University of Palemban
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
autor
- Chemical Engineering Department, Faculty of Engineering, Muhammadiyah University of Palembang
Bibliografia
- [1] Muhammad, u., Yan, p., & Riri, p, 2017. KP report data of PT. Pertamina (Persero) Refinery unit 3 Plaju-Sungai Gerong. Palembang.
- [2] Adrial, M. (2008). Short circuit fault and protection of the electric power system. coordination planning studies, 2-15.
- [3] John J. Grainger., William D. Stevenson. Power system analysis. International Editions. McGraw-Hill, Inc. 1994.
- [4] William D. Stevenson, Jr. (1983). Analysis of the electric power system 4th edition. Erlangga publisher, Jakarta 1993.
- [5] Amira, & Asnal, e. (2014). analysis study of single phase short circuit to ground at 150 KV SUTT for OCR relay setting (GI PIP-Pauh limo application). Journal of Electrical Engineering ITP Vol. 3 No. 2 , 1-10.
- [6] Yusnan, b., & rizki, l. (2013). performance of the Ground fault relay (soil fault relay) at feeders 4 and 6 of the Srondol substation. ISSN : 2254-4908 Vol.2 no.3, 215-224.
- [7] Muhammad, T. (2006). Electrical Power System Protection. Malang: Faculty of Electrical Engineering, Islamic University of Malang
- [8] Muhammad, ik (2016). Analysis of the ground fault relay (GFR) setting on the neutral grounding system of the Pandeanlamper 06 JTM 20 kV Semarang feeder. 22-77.
- [9] Yusmartanto, & Yusniati. (2016). Analysis of overcurrent relays and ground fault relays on the LM 5 feeder at the Lamhotma Substation. journal of electrical technology, Vol. 1 No.2 ISSN:2502-3624 , 1-11.
- [10] http://repo.unand .ac.id /3434/1/short circuit study for symmetrical and asymmetrical faults in electric power systems.pdf
Uwagi
Opracowanie rekordu ze środków MEiN, umowa nr SONP/SP/546092/2022 w ramach programu "Społeczna odpowiedzialność nauki" - moduł: Popularyzacja nauki i promocja sportu (2022-2023).
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-e0119dbb-97fe-4174-968b-cc7ef89c57f6