The paper analyses the impact that the construction of water mist extinguishers exerts on the size of generated drops. The test was based on the examination of three extinguishers of two producers, which have been available in the market in recent years. The test was carried out with the use of the IPS Drop Spectrum Analyzer (DSA). The device operates by using the photoelectric method to measure the parameters of the extinguishing stream microstructure. There were two measuring ranges: 0_1 414 μm and 0_2 658 μm. The test results present mean diameters of the generated drops, aggregated curves representative of their share as well as the analysis of the quality of spraying the extinguishing medium. The tests have shown that two out of three tested extinguishers do not generate water mist with standard parameters at a distance of 170 cm. The smallest mean diameters of drops were generated by extinguisher B, whereas the biggest ones by extinguisher C The highest level of spraying among all samples was found for extinguisher B. It’s Sauter diameter mean amounted to 564.03 μm. Further, it was shown what impact the construction of water mist extinguishers exerts on the size of generated drops.
Czasopismo
Rocznik
Tom
Strony
99--104
Opis fizyczny
Bibliogr. 16 poz.
Twórcy
autor
- Eng.; The Main School of Fire Service, Słowackiego 52/54, 01-690 Warsaw
Bibliografia
- [1] CEN/TS 14972:2011: Fixed firefighting systems - Watermist systems - Design and installation.
- [2] Gałaj J, Masternak M. (2012). Badanie własności strumienia rozpylonego generowanego przez prądownicę wodną z głowicą mgłową (Investigation properties of the spray generated by a water nozzle with a fog head). Technika Transportu Szynowego 9, 219-232.
- [3] Han Z, Zhang Y, Du Z, Xu F, Li S, Zhang J. (2017). New-type gel dry-water extinguishants and its effectiveness. J. Clean, 166, 590-600.
- [4] Haynes W. M. (2016). CRC Handbook of Chemistry and Physics, Boca Raton.
- [5] KAMIKA (1999). Zakład Elektronicznej Aparatury Pomiarowej “AWK SYSTEM”. Analiza Wielkości Cząstek KμK.
- [6] Lee J. (2019). Numerical analysis on the rapid fire suppression using a water mist nozzle in a fire compartment with a door opening. Nuclear Engineering and Technology, 51(2), 410-423.
- [7] Liu Z.G, Kim A.K. (2001). A Review of water mist fire suppression technology: Part II - Application studies Journal of Fire Protection Engineering, 11/1.
- [8] Liu Z., Kim A.K., Carpenter D. (2007). A study of portable water mist fire extinguishers used for extinguishment of multiple fire types. Fire Safety Journal, 42, 25-42.
- [9] NFPA 750 Standard on Water Mist Fire Protection Systems - 2019 Edition.
- [10] Norma PN-EN 3-7+A1:2008 - Gaśnice przenośne. Part 7. Charakterystyka, wymagania eksploatacyjne i metody badań.
- [11] Orzechowski Z, Prywer J. (1991). Rozpylanie cieczy 2nd edition WNT, Warszawa.
- [12] Orzechowski Z, Prywer J. (1997). Mechanika płynów w inżynierii środowiska WNT, Warszawa.
- [13] Roguski J., Zbrożek P., Czerwienko D. (2012). Wybrane aspekty stosowania w obiektach budowlanych urządzeń gaśniczych na mgłę wodną. Teoretyczne podstawy rozpylania cieczy, pomiary struktury mgły, działanie mgły w środowisku pożaru oraz kryteria doboru urządzeń gaśniczych na mgłę wodną, zastosowanie urządzeń gaśniczych mgłowych ze szczególnym uwzględnieniem obiektów zabytkowych. Publishing House: Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej im. Józefa Tuliszkowskiego - Państwowy Instytut Badawczy, Józefów.
- [14] Santangelo P.E., Tartarini P. (2010). Fire control and suppression by water-mist systems. The Open Thermodynamics Journal 4, 167-184.
- [15] Zhou Y, Bu R, Gong J, Zhang X, Fan X, Wang X. (2018). Assessment of a clean and efficient fire-extinguishing technique: Continuous and cycling discharge water mist system. Journal of Cleaner Production, 182.
- [16] Zhou Y, Bu R, Zhang X, Fan X, Gong J. (2019). Performance evaluation of water mist fire suppression: A clean and sustainable fire-fighting technique in mechanically-ventilated place. Journal of Cleaner Production, 209.
Uwagi
PL
Opracowanie rekordu ze środków MNiSW, umowa Nr 461252 w ramach programu "Społeczna odpowiedzialność nauki" - moduł: Popularyzacja nauki i promocja sportu (2020).
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-d737134a-f3b9-4dfb-84e2-14ce7a66b14c