Tytuł artykułu
Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
Wyznaczanie okresowego obciążenia prądowego kabla jednożyłowego XLPE z uwzględnieniem znamionowego czasu życia
Języki publikacji
Abstrakty
This paper provides an overview of overload capacity of single-core XLPE cables buried in the ground. Cyclic rating factor obtained by IEC60853-1 and IEC60853-2 standards is conservative due to assumption that maximum temperature during the cycle is equal to rated temperature. Using the procedure proposed by IEC60853-2, transient temperature response of the cables exposed to daily cyclic loading is calculated. Then, overload capacity of cables is obtained with respect to assigned design life of cables using Arrhenius-IPM electrothermal life model.
W artykule przedstawiono wyniki analizy możliwości przeciążeniowych jednożyłowego kabla grzebanego w ziemi. Na podstawie procedury zawartej w standardzie IEC60853-2 określono wpływ dobowego obciążenia energetycznego na zmiany temperatury kabla. Następnie korzystając z modelu elektro-termalnego Arrhenius-IPM i uwzględniając dane znamionowe określono możliwości przeciążeniowe kabli.
Wydawca
Czasopismo
Rocznik
Tom
Strony
152--156
Opis fizyczny
Bibliogr. 10 poz., rys., tab.
Twórcy
autor
- University of Nis, Faculty of Electronic Engineering
autor
- University of Nis, Faculty of Electronic Engineering
autor
- University of Nis, Faculty of Electronic Engineering
Bibliografia
- [1] Neher J.H., McGrath M.H., The Calculation of the Temperature Rise and Load Capability of Cable Systems, AIEE Transactions, Power Apparatus and Systems, 76 (1957), No. 3, 752-772
- [2] Anders G.J.,El-Kady M.A., Transient Rating of Buried Power Cables, Part 1: Historical Perspective and Mathematical Model, IEEE Trans. Power Delivery, 7 (1992), No.4, 1724-1734
- [3] Anders G.J., Rating of Electric Power Cables in Unfavorable Thermal Environment, New York, Wiley-IEEE Press, 2005
- [4] Calculation of the Cyclic and Emergency Current Ratings of Cables, Part 1: Cyclic Rating Factor for Cables up to and Including 18/30 (36) kV, IEC Std. 60853-1, 1985
- [5] Calculation of the Cyclic and Emergency Current Ratings of Cables, Part 2: Cyclic Rating Factor of Cables Greater than 18/30 (36) kV and Emergency Ratings for Cables of All Voltages, IEC Std. 60853-2, 1989
- [6] Mazzanti G., Montanari G. C., A Comparisom between XLPE and EPR as Insulated Materials for HV Cables, , IEEE Trans. On Power Delivery, 12 (1997), No. 1, 15-28
- [7] Mazzanti G., Analysis of the Combined Effects of Load Cycling, Thermal Transients and Electrothermal Stress on LifeExpectancy of High Voltage AC Cables, IEEE Trans. Power Delivery, 22 (2007), No.4, 2000-2009
- [8] Mazzanti G., The Combination of Electro-thermal Stress, Load Cycling and Thermal Transients and its Effects on the Life of High Voltage AC Cables, IEEE Trans. On Dielectrics and Electrical Insulation, 16 (2009), No. 4, 1168-1179
- [9] Abramowitz M., Stegun I., Handbook of Mathematical Functions, New York, Dover Publications, INC., 1972
- [10] XLPE Land Cable Systems, ABB, User’s Guide, 5 (2010)
Typ dokumentu
Bibliografia
Identyfikator YADDA