PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Research on Current Interruption by Grounding switch Used in 750kV Double-circuit Transmission Lines

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Badania prądu przerwania w uziemionym przełączniku używanym w podwójnej linii transmisyjnej 750 kV
Języki publikacji
EN
Abstrakty
EN
In order to interrupt electromagnetically and electro-statically inductive current with high amplitude, grounding switches are applied in double-circuit transmission lines. In this paper, the formula of the induced voltage and current are drawn under different condition of grounding switch installed on the maintenance line. In order to clarify the characteristics of every electrical parameter, after calculating the capacitance and inductance matrix of 750kV double circuit transmission lines, simulation research is conducted using EMTP-ATP. Inductive voltage and current of 750kV doublecircuit transmission line are calculated and analyzed. Furthermore, in order to classify the worst switching parameter of grounding switches, the steady-state currents and the transient recovery voltage (TRV) are also calculated and analyzed. And then, the tests of capacitive and inductive current interruption for a 800kV grounding switch are also carried out in the laboratory. The results of the simulation and experiment in this paper provide guiding opinions for selecting grounding switches used in the 750kV double-circuit transmission lines.
PL
W pracy określano zależności prądu i napięcia indukowanego w uziemionym przełączniku przy różnych warunkach pracy. Obliczono pojemność i indukcyjność linii transmisyjnej 750 kV a następnie symulowano przebiegi prądów.
Rocznik
Strony
109--114
Opis fizyczny
Bibliogr. 13 poz., rys., tab.
Twórcy
  • State Key Laboratory of Electrical Insulation and Power Equipment, Department of electric engineering, Xi′an Jiaotong University
autor
  • Guangdong Electric Power Research Institute, Guangzhou,China
Bibliografia
  • [1] Shu YinBiao; Zhao ChengHua. "Study and implementation of 500kV compact power transmission line with double circuits on a same tower in china". Power System Technology, Vol. 26, No. 4, pp. 49-53, 2002.
  • [2] Abdul M.Mousa. "Ground Switch Interrupting Duty and Total Ground Current Imposed by Induction FromParallel Transmission Lines: Part I – Theoretical Analysis". CEA Paper No.81-TR-243, Trans. CEA Engineering and Operating Division, vol. 20, part 5, 16 pages, 1981.
  • [3] Abdul M.Mousa. "Ground Switch Interrupting Duty and Total Ground Current Imposed by Induction From Parallel Transmission Lines: A Quantitative Analysis for the Range 69kV-1150kV". IEEE Transactions on Power Apparatus and Systems, Vol. 100, No. 8, pp. 3839-3849, 1981.
  • [4] Habedank U, Luehrmann H. "Stresses on grounding switches during opening". IEEE Transactions on Power Apparatus and Systems, Vol. 104, No. 5, pp. 1225 – 1232, 1985.
  • [5] Hu Yi, Nie Ding-Zhen. "Calculation of Induced Voltage and Safety Working Condition on 500 kV Double Circuit Transmission Lines". Electric Power, Vol. 33, No. 6, pp. 45-47, 2000.
  • [6] Hu Dan-Hui, Tu Cai-Qi, Jian Wei. "Calculation of Inductive Voltage and Current for 500kV Double Circuits Transmission Lines On Single Tower". High Voltage Engineering, Vol. 34, No.9, pp1927-1931, 2008.
  • [7] Guo Xian-shan. "Questions of HV Earthing Switch Switching induced Current". High Voltage Apparatus, Vol. 42, No. 3, pp. 214-219, 2006.
  • [8] Mizoguchi, H., Yokota, T., and et al. "Development of an interrupting chamber for 1000 kV high-speed grounding switches". IEEE Transactions on Power Delivery, Vol. 13, No.2, pp. 495-502, 1998.
  • [9] Liqun Shang, Wei Shi. "Investigation of the secondary arc current and the recovery voltage on a double-circuit transmission lines". IEEE Power Engineering Society General Meeting, Denvor, USA, Vol.2, pp. 1209-1213, 2004.
  • [10] Lei Chen, Haijun Liu, Ming Wu, and et al. "Study on Compensation for Secondary Arc Current on UHV Double-Circuit Lines". Power and Energy Engineering, Conference (APPEEC), Wuhan, China, pp.1-4, 2011.
  • [11] Liqun Shang, Wei Shi. "Study of the Secondary Arc Extinction at EHV Double Circuit Transmission Lines". Automation of Electric Power Systems, Vol. 29, No.10, pp. 60-64, 2005.
  • [12] He Baina, Lin Xin, Xu Jianyuan. "The Analysis of Secondary Arc Extinction Characteristics on UHV Transmission Lines". International Conference on High Voltage Engineering and Application, pp. 516-519, Chongqing, China, 2008.
  • [13] H.W.Dommel. "EMTP Theory Book". Microtran Power System Analysis Corporation Vancouver, British Columbia, May,1992.