In this paper a numerical model was created for the combustion chamber of BP 1150 boilers of Opole Power Plant with an additional set of protection air system nozzles. The calculation was using Ansys Fluent CFD. Three cases of air distribution to OFA and SOFA nozzles were modeled. The ratio of air was increased to OFA and SOFA nozzles by taking secondary air from burners to decrease NOx emission. The distribution of primary and secondary air was done so that the ratio of air from the protection air system was at a stable 10% of secondary air. A numerical simulation of the furnace of BP 1150 boilers confirmed that staggered air decreases NOx emission and showed the NOx concentrations at various levels of the combustion chamber.
Rocznik
Strony
34--47
Opis fizyczny
Bibliogr. 4 poz., tab., rys.
Twórcy
autor
  • Institute of Power Engineering and Turbomachinery, Silesian University of Technology, 20 Konarskiego Street, 44-100 Gliwice, Poland, bartlomiej.hernik@polsl.pl
Bibliografia
  • [1] The Minister of Environment of 20 December 2005 on emission standards for installations [Rozporządzenie Ministra Środowiska z dnia 20 grudnia 2005 r. w sprawie standardów emisyjnych z instalacji].
  • [2] Directive 2001/80/ec of the european parliament and of the council of 23 october 2001.
  • [3] B. Hernik, R. Litka, Selection of velocity and quantity of secondary air to the burners and nozzles OFA [dobór prędkości i ilości powietrza wtórnego do palników i dysz OFA], Tech. rep., unpublished.
  • [4] B. Hernik, Research to reduce the risk of corrosion and erosion of power boilers [badania dla zmniejszenia zagrożenia korozyjno-erozyjnego kotłów energetycznych], Ph.D. thesis, Silesian University of Technology, Gliwice (2009).