PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Measurement of flow rate in square-sectioned duct bend

Treść / Zawartość
Identyfikatory
Warianty tytułu
PL
Pomiar strumienia płynu w kanale z łukiem kolana o przekroju kwadratowym
Języki publikacji
EN
Abstrakty
EN
In this paper the authors describe an attempt to utilise installed square- sectioned elbows in order to measure the fluid flow rate. In order to practically accomplish the measurement of the volumetric flow rate of the air, a special research stand has been built, and square shaped elbows have been installed (80 × 80mm in dimension). The numerical computations were carried out using the software package FLUENT 6.2. The obtained results were compared to corresponding ones coming from orifice measurements and from experimental work available in the literature. The comparative analysis of the obtained numerical and experimental results evidenced a high degree of their conformity.
PL
W pracy podjęto próbę wykorzystania zainstalowanych w kanałach przepływowych łuków kolan o przekroju kwadratowym do pomiaru strumienia objętości płynu. W tym celu wykorzystano opracowaną wcześniej metodę pomiaru pośredniego dla rurociągów o przekroju kołowym. Dla praktycznej realizacji pomiaru wspomnianego strumienia przepływu zbudowano stanowisko badawcze za łukiem kolana o przekroju poprzecznym w kształcie kwadratu (80 × 80mm). Obliczenia wykonano za pomocą pakietu FLUENT 6.2. Uzyskane rezultaty porównano z odpowiednimi zmierzonymi za pomocą kryzy pomiarowej oraz z innymi wynikami doświadczalnymi dostępnymi w literaturze. Z analizy porównawczej wynika wysoki stopień zgodności otrzymanych rezultatów pomiaru pośredniego.
Rocznik
Strony
301--311
Opis fizyczny
Bibliogr. 9 poz., rys., tab.
Twórcy
autor
autor
Bibliografia
  • 1. Bean H.S., 1971, Fluid Meters; Their Theory and Application, 6ed Ed., ASME
  • 2. Fluent 6.2, 2008, User’s Guide, Fluent Inc.
  • 3. Malinowski Ł., Rup K., 2008, Measurement of the fluid flow rate with use of an elbow with oval cross section, Flow Measurement and Instrumentation, 19, 358-363
  • 4. PN-EN ISO 5167-1, 2004, Measurement of fluid flow by means of pressure differentia devices inserted in circular cross-section conduits running full – part 1: General principles and requirements, and part 2: Orifice plates
  • 5. Rup K., Malinowski Ł., 2005, Metoda pomiaru strumienia objętości płynu w zastosowaniach do przepływomierzy kolanowych, PAK, 5, 35-37
  • 6. Rup K., Malinowski Ł., 2006, Fluid flow identification on base of the pressure difference measured on the secant of a pipe elbow, Forschung im Ingenieurwesen, 70, 199-206
  • 7. Spitzer D.W., 2001, Flow Measurement – Practical Guides for Measurement and Control, 2nd Ed., ISA
  • 8. Sudo K., Sumida M., Hibara H., 2001, Experimental investigation on turbulent flow in a square-sectioned 90-degree bend, Experiments in Fluids, 30, 246-252
  • 9. Taler J., Duda P., 2006, Solving Direct and Inverse Heat Conduction Problems, Springer, Berlin
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BWM6-0005-0016
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.