Application of on-line respiratory measurement for wastewater treatment plants control

Identyfikatory
Warianty tytułu
PL
Wykorzystanie ciągłych pomiarów zużycia tlenu do kontroli pracy oczyszczalni ścieków
Języki publikacji
EN
Abstrakty
EN
In order to keep the WWTP performance under control and to make decisions of minimizing the potential influence of wastewatcr components on the stable and proper WWTP operation, the devices for on-line control of oxygen uptake rate were designed and manufactured. The devices were used for three aims: - controlling the presence of harmful substances for microorganisms in raw wastcwater (Toximctcr), -assessment of the real physiological condition of activated sludge in the aeration chamber (Activmctcr), -determining of the effects of activated sludge settling properties deterioration and its influence on the secondary clarificrs operation as well as microorganisms presence in treated wastcwater (Sedimctcr). The results confirmed that the devices arc helpful for the WWTP operators as an early warning system and enable optimal decisions making.
PL
Efekt oczyszczania ścieków zależy od właściwego zaprojektowania, wykonania i eksploatacji oczyszczalni. Ze względu na zmienność składu ścieków surowych, a w tym obecność związków toksycznych, bardzo istotne dla stabilnej pracy oczyszczalni jest wcześniejsze wykrywanie obecności tych składników w dopływających ściekach. Powinno to pozwolić na ustalenie ewentualnego sprawcy zagrożenia przez pobór próbek do analizy z chwilą pojawienia się sygnału o obecności związków toksycznych dopływających w ściekach, jak również na podjęcie zabiegów niwelujących ich wpływ na biologiczny stopień oczyszczalni ścieków. Do oceny toksycznego efektu składu ścieków wykorzystać można bardzo różne metody. Zaprojektowany uniwersalny aparat do ciągłego oznaczania aktywności mikroorganizmów umożliwia stały i skuteczny nadzór nad oczyszczaniem ścieków. Zasada działania aparatu polega na pomiarze tzw. aktywności metabolicznej drobnoustrojów, której miarą jest szybkość zużywania tlenu na ich procesy życiowe. Aparat ten spełniać może trzy odmienne role: - umiejscowiony bezpośrednio w bioreaktorze, w którym zachodzą procesy oczyszczania informować będzie o aktualnej "kondycji" drobnoustrojów i jej wahaniach (aktywometr); - umiejscowiony na kanale dopływowym ścieków surowych może informować o zawartych w nich substancjach.
Rocznik
Strony
25--31
Opis fizyczny
bibliogr. 12 poz., wykr.
Twórcy
autor
autor
autor
  • Silesian University of Technology, Department of Environmental Biotechnology ul. Akademicka 2,44 100 Gliwice, Poland
Bibliografia
  • [1] Elnabarawy M.T., R.R Roideau, A.A Beach: Comparison of three toxicity test procedures: Microtox, Polytox and activated sludge inhibition, Toxicity Assessment, 3, 361-370 (1988).
  • [2] Geenens D., C. Thocyc : The use of an on-line respirometer of the screening of toxicity in the Antwerp WWTP catchment area, Wat. Sci. Tech., 37(12), 213-218 (1998).
  • [3] Gernacy K., L. Verschuere, L. Luyten, W. Verstrate: Fast and sensitive acute toxicity detection with an enrichment nitrifying culture, Wat. Environ. Res., 69, 1163-1169 (1997).
  • [4] Kim C.-W., B.-G. Kim, T-H. Lec, T.-J Park: Continuous and early detection of toxicity in industrial wastewater using an on-line respiration meter, Wat. Sci. Tech., 30(3), 11-19 (1994).
  • [5] Klapwijk A., H. Spanjers, H. Temmink: Control of activated sludge plants based on measurement of respiration rates, Wat. Sci. Tech., 28(11-12), 369-376 (1993).
  • [6] Miksch K.: Biochemische Bewertungsmethoden der Belebtschlammaktivitat, Gcwasscrschutz-Wasser-Abwasscr, 62, 509-532 (1985).
  • [7] Miksch K., B. Schumann: Toxizitatsbestimmung von Zinksulfat, Kupfersulfat und Phenol anhand ver-schiedener Methoden, Z. Wasscr-Abwasscr-Forsch., 21, 193-198 (1988).
  • [8] Miksch K., J. Surmacz-Górska, P. Ostrowski: The assessment of toxicity and shock-loading on activated sludge by means- of on-line respiratory measurements (2007) (in preparation).
  • [9] Spanjers H., P. Vanrolleghem, K. Nguyen, H. Vanhooren, G.G. Patry: Towards a simulation-benchmark for evaluating respirometry based control strategies, Water Sci. Tech., 37(12), 219-226 (1998).
  • [10] Surmacz-Górska J., K. Gemaey, C. Demuynck, P.A Vanrolleghem, W. Verstraete: Nitrification process control in activated sludge using oxygen uptake rate measurements, Environ. Technol., 16, 569-577 (1995).
  • [11] Temmink H., P.A Vanrolleghem, A. Klapwijk, W. Verstraete: Biological early warning systems for toxicity based on activated sludge respiration, Wat. Sci. Tech., 28(11/12), 415-425 (1993).
  • [12] Vanrolleghem P.A., Z. Kong, G. Rombouts, W. Verstraete: An on-line respirographic biosensor for the characterization of load and toxicity ofwastewaters, J. Chem. Tech. Biotechnol., 59, 321-333 (1994