Influence of the method of the control of the hybrid contactless short-circuit limiter on power quality

Autorzy
Treść / Zawartość
Identyfikatory
Warianty tytułu
PL
Wpływ sposobu sterowania bezstykowego hybrydowego ogranicznika prądów zwarciowych na jakość energii
Języki publikacji
EN
Abstrakty
EN
The paper is dedicated to control conditions of a hybrid contactless current limiter aimed at the efficient mitigation of voltage dips. Basic features of the limiter, as well as its control circuit have been described. Since the fault current is detected by operation of a special short fuse incorporated in the limiter the control has to be tuned to the prearcing and arcing times of the fuse dependent on actual current and circuit conditions. It has been demonstrated that the control system based on the across-fuse voltage measurement needs relevant fast-acting sensors. Effects of timing of the limiter control on the fault current limitation have been demonstrated.
PL
W artykule przedstawiono wpływ sterowania bezstykowego ogranicznika prądów zwarciowych na ograniczanie zapadów napięcia. Scharakteryzowano podstawowe własności ogranicznika oraz układu sterowania jego pracą. Ponieważ prąd zwarciowy jest detekowany przez dedykowany superkrótki bezpiecznik sterowanie musi być dostosowane do czasu przedrukowego i łukowego topika, które zależą od aktualnej wartości prądu i aktualnej konfiguracji obwodu. Pokazano, że układ sterowania oparty na pomiarze napięcia miedzy zaciskami topika wymaga zastosowania bardzo szybkiego czujnika pomiarowego. Zaprezentowano wpływ doboru czasów sterowania ogranicznika na ograniczanie prądu zwarciowego.
Wydawca
Rocznik
Strony
98--101
Opis fizyczny
Bibliogr. 9 poz., rys., wzory
Twórcy
  • Faculty of Electrical and Control Engineering, High Voltage and Electrical Apparatus, Gdańsk University of Technology, p.lesniewski@ely.pg.gda.pl
Bibliografia
  • [1] PN-EN 50160:1998: Parametry napięcia zasilającego w publicznych sieciach rozdzielczych.
  • [2] Wolny A., Semenowicz B.: Hybrid contactless short-circuit current limitation. 10-th International Symposium on "Short Circuit in Power Systems", Lodz, 28-29 October 2002.
  • [3] Wolny A.: A new method of current limitation, Seventh International Conference of Electric Fuses and their applications, 8-10 September, Junta 2003.
  • [4] Wolny A., Semenowicz B., Leśniewski P: Features of a short fuse, as a main current path of a contactless hybrid current limiter. 10-th International Symposium on "Short Circuit in Power Systems", Łódź, 28-29 October 2002.
  • [5] Semenowicz B.: Bezpiecznik krótkotopikowy jako element bezstykowego hybrydowego ogranicznika prądów, Rozprawa doktorska (maszynopis), Gdańsk 2006.
  • [6] Czucha J.: Arc ignition process in short fuse elements. Seventh International Conference of Electric Fuses and their applications, 8-10 September, Jurata 2003.
  • [7] Lipski T.: Bezpieczniki niskonapięciowe, WNT Warszawa 1968.
  • [8] Semenowicz B., Partyka R.: Dielectric strength of the ultra-short fuse, Seventh International Conference of Electric Fuses and their applications, 8-10 September, Jurata 2003.
  • [9] Leśniewski P., Tłustochowicz L.: Wpływ sterowania ogranicznika prądów zwarciowych na jakość energii elektrycznej. Zeszyty naukowe Wydziału Elektrotechniki i Automatyki Politechniki Gdańskiej Nr 21, Gdańsk 2005.