PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Experimental study of anti-scale devices efficiency

Autorzy
Identyfikatory
Warianty tytułu
Języki publikacji
EN
Abstrakty
EN
The flow of real liquid through the water pipes is connected with the generation of head losses. During the operation of the water pipes scales tend to build up on their walls. This causes reduction of a pipe diameter and as a result increases the hydraulic resistance and decreases the water capacity as well as worsens the water quality. One of the methods used to reduce the accumulation of water scale deposits in water pipes is application of the Magnetic Water Treatment technology. A special test rig was constructed. It was designed to monitor the change in head losses values of the steel pipes under the influence of the magnetically conditioned water. Magnetic devices used in this study are of a different construction and field strength. Studies were performed for three different flow velocities – 0.5, 0.7, 0.9 [m/s] (in test pipes), time period for each of them was 65 days. The results for the MWT devices were compared with the results gathered for test pipes with no device installed, with ION device and with a dummy magnetic device with an inert core. For each case, a graph of the distribution of the hydraulic loss values in time was plotted and a curve was fitted to it. Studies show that the use of the magnetic technology can be an efficient mean of scaling control. They also show how the results depend on the hydraulic parameters and the construction of the devices.
PL
Przepływ cieczy w przewodach wodociągowych związany jest z generowaniem strat na długości, nazywanych inaczej stratami liniowymi. W trakcie eksploatacji stalowych instalacji wodociągowych obserwuje się wytrącanie osadów na ściankach rur. Zjawisko to powoduje redukcje przekroju przewodu, a przez to zwiększenie oporności hydraulicznej instalacji, obniżenie jej przepływności, a także wpływa niekorzystnie na jakość wody. Jednym ze sposobów zabezpieczania stalowych systemów wodociągowych przed ww. niekorzystnym wpływem akumulacji osadów jest stosowanie urządzeń działających w oparciu o pole magnetyczne. W celu sprawdzenia ich działania skonstruowano układ doświadczalny, który pozwolił na śledzenie zmian wartości strat hydraulicznych przewodów stalowych zachodzących pod wpływem działania wody poddanej działaniu urządzeń magnetycznych (o różnej konstrukcji i wartości indukcji pola). Badanie prowadzono dla trzech różnych prędkości przepływu wody w przewodzie – 0.5, 0.7, 0.9 [m/s] w okresie 65 dób dla każdej. Otrzymane wyniki zestawiono z wynikami dla przewodów porównawczych oraz dla urządzenia działającego w oparciu o efekt ogniwa galwanicznego, następnie do rozkładu zmian ciśnienia dopasowano odpowiednie funkcje. Badania pokazały możliwość zastosowania ww. urządzeń do minimalizacji inkrustacji osadami przewodów wodociągowych, ukazały także ich zależność od parametrów hydraulicznych oraz konstrukcyjnych urządzeń.
Rocznik
Strony
117--126
Opis fizyczny
Bibliogr. 18 poz.
Twórcy
  • Faculty of Energy and Environmental Engineering, The Silesian University of Technology, Konarskiego 18A, 44-100 Gliwice, Poland, lukas.skorkowski@polsl.pl
Bibliografia
  • [1] Baker J.S., Judd S.J.; Magnetic amelioration of scale formation. Elsevier Science Ltd., Water Research Vol. 30, No. 2, p.247-260,1996
  • [2] Brower J.; Magnetic Water Treatment, Pollution Engineering, No. 2, p.26-28, Feb 2005
  • [3] Endress+Hauser; Przepływomierz elektromagnetyczny Promag 50, Instrukcja obsługi. (Electromagnetic Flow Measuring System Promag 50, Operating Instructions) BA 046D/06/pl/04.00 (in Polish)
  • [4] Endress+Hauser; Przetwornik różnicy ciśnień Deltabar S, Instrukcja obsługi, BA 174P/00/pl/07.98a. (Differential pressure transmitter Deltabar S, Operating Instructions) (in Polish)
  • [5] Gabrielli C., Jaouhari R., Maurin G., Keddam M.; Magnetic water treatment for scale prevention. Elsevier Science Ltd., Water Research Vol. 35, No. 13, p.3249-3259, 2001
  • [6] Grajper P.; Eksperymentalne wyznaczenie miejscowych strat ciśnienia w kolanach 90º współczesnych systemów instalacyjnych. Rozprawa doktorska (Experimental determination of the minor head loss in the 90° elbows in modern plumbing systems. PhD thesis) - Instytut Inżynierii Wody i Ścieków Zakład Wodociągów i Kanalizacji, Politechnika Śląska, Gliwice 2004 (in Polish)
  • [7] Kołodziejczyk L., Mańkowski S., Rubik M.; Pomiary w inżynierii sanitarnej. (Measurements in sanitation engineering) Arkady, Warszawa 1974 (in Polish)
  • [8] Krogulska B., Wichrowska B.; Wpływ instalacji wodociągowych na jakość wody. (Influence of indoor plumbing systems on the water quality) Polski Instalator 2/94 (in Polish)
  • [9] Krope J., Kozic V., Tiar I., Kiker E.; Laboratory measurements on magnetic water treatment device, IECON'01: The 27th Annual Conference of the IEEE Industrial Electronics Society, p.2190-2193, Denver 2001
  • [10] Lehtolaa M.J., Miettinena I.T., Keinanena M.M., Kekkia T.K., Laineb O., Hirvonenc A., Vartiainenb T., Martikainenc P.J.; Microbiology, chemistry and biofilm development in a pilot drinking water distribution system with copper and plastic pipes. Water Research Vol. 38, p. 3769-3779, Elsevier Science Ltd, 2004
  • [11] Magnet-Physik Dr.Steingroever GmbH; Miernik natężenia pola magnetycznego FH 54, Instrukcja obsługi. (Magnetic Field Strength Meter Gaussmeter/Teslameter FH 54, Operating Instructions) BA 0420020102 (in Polish)
  • [12] McNeill L.S., Edwards M.; Iron pipe corrosion in distribution system. Journal AWWA, July 2001, p.88-100
  • [13] Percival S.L., Knapp J.S., Edyvean R.G.J., Wales D.S.; BIOFILMS, MAINS WATER AND STAINLESS STEEL, Water Research Vol.32, No.7, p.2187-2201, Elsevier Science Ltd, 1998
  • [14] PN-EN 6817:1996; Pomiar strumienia masy lub strumienia objętości cieczy przewodzącej w przewodach. Metoda z zastosowaniem przepływomierzy elektromagnetycznych. (Measurement of conductive liquid. Flow in closed circuits - methods using electromagnetic flowmeters) (in Polish)
  • [15] PN-EN ISO 5167-1:2005; Pomiary strumienia płynu za pomocą zwężek pomiarowych. Kryzy, dysze, zwężki Venturiego wbudowane w całkowicie wypełnione rurociągi o przekroju kołowym. (Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full - Part 1: General principles and requirements) (in Polish)
  • [16] PN-ISO 4064-3:1997; Pomiar objętości wody w przewodach. Wodomierze do wody pitnej zimnej. Metody badań i wyposażenie. (Measurement of water flow in fully charged closed conduits - Meters for cold potable water and hot water - Part 3: Test methods and equipment) (in Polish)
  • [17] StatSoft, Inc. (2007). Electronic Statistics Textbook. Tulsa, (http://www.statsoft.com/textbook/stathome.html), StatSoft, 2007
  • [18] Wang Y., Babcin A.J., Chernyi L.T., Chow R.S., Sawatzky R.P.; Rapid onset of calcium carbonate crystallization under the influence of a magnetic field, Elsevier Science Ltd., Water Research Vol.31, No.2, p.346-350,1997
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BSL6-0012-0013
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.