How can the IRP p-q theory be applied for active filtering under nonsinusoidal voltage operation?

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Jak teoria IRP p-q może być użyta do filtracji aktywnej w warunkach niesinusoidalnego napięcia?
Języki publikacji
EN
Abstrakty
EN
This paper presents an analysis of Akagi's p-q theory for active filtering under nonsinusoidal voltage conditions. It is ascertained that compensating the alternative parts of the instantaneous active and reactive powers leads to a sinusoidal power supply current only under sinusoidal voltage conditions. A modified definition of the active component of the current is proposed for operation under nonsinusoidal voltage conditions and shunt active filter applications. A generic example and the full controlled rectifier-based DC motor drive system are used as case studies.
PL
Artykuł przedstawia analizę teorii p-q Akagi'ego, stosowanej do filtracji aktywnej w warunkach napięć niesinusoidalnych. Stwierdzono, że kompensacja składników oscylacyjnych mocy chwilowych, czynnej i biernej, prowadzi do sinusoidalnego prądu zasilania tylko w warunkach zasilania napięciem sinusoidalnym. Zaproponowano zmodyfikowaną definicję składowej czynnej prądu na potrzeby sterowania równoległego filtru aktywnego pracującego przy niesinusoidalnym napięciu zasilania. Prostownikowy napęd silnika prądu stałego został użyty w artykule jako przykład dla przedstawionej w artykule analizy.
Rocznik
Strony
67--71
Opis fizyczny
Bibliogr. 18 poz., rys.
Twórcy
autor
autor
  • Electric Drivers and Industrial Informatics Department, Faculty for Electromechanical, Environmental and Industrial Informatics Engineering, University of Craiova, Romania, Decebal Bd. 107, 200440 Craiova, abitoleanu@em.ucv.ro
Bibliografia
  • [1] Nedelcu V.N., Die einheitliche leistungstheorie der unsymetrischen und mehrwelligen mehrphasensysteme, ETZ-A Elektrotech. Z., 84 (1963) No. 5, 153-157
  • [2] Nedelcu V.N., Electromechanical conversion theory, Technical Ed., Bucharest, 1978. (In Romanian)
  • [3] Akagi H. and Nabae A., The p-q theory in three-phase systems under non-sinusoidal conditions, European Trans. on Electrical Power, 3 (1993), No.1, 27-31
  • [4] Akagi H., New trends in active filters for power conditioning, IEEE Trans. Ind. Appl., 32 (1996), No. 6, 1312-1322
  • [5] Emanuel A.E., Powers in nonsinusoidal situations: A review of definitions and physical meaning, IEEE Trans. on Power Delivery, 5 (1990), No. 3, 1377-1389
  • [6] Emanuel A.E., On the definition of power factor and apparent power in unbalanced polyphase circuits with sinusoidal voltage and currents, IEEE Trans. on Power Delivery, 8 (1993), No. 3, 841-852
  • [7] Slonim M.A. and Van Wyk J.D, Power components in a system with sinusoidal and nonsinusoidal voltages and/or currents, Proc. IEE, 135 (1988) Issue 2, 76-84
  • [8] Willems J.L., Critical analysis of the concepts of instantaneous power currents and of active current, European Trans. on Electrical Power, 8 (1998), 271-274
  • [9] Willems J.L., Current compensation in three-phase power systems, European Trans. on Electrical Power, 3 (1993), Issue 1, 61 – 66
  • [10] Czarnecki L.S., On some misinterpretations of the instantaneous reactive power p-q theory, IEEE Trans. on Power Electronics, 19 (2004), No. 3, 828-836
  • [11] Czarnecki L.S., Orthogonal decomposition of the current in a three phase nonlinear asymmetrical circuit with nonsinusoidal voltage, IEEE Trans. on Instrum. Meas., IM-37 (1988), No. 1, 30–34
  • [12] Czarnecki L.S., Physical interpretation of the reactive power in terms of the CPC power theory, Electrical Power Quality and Utilisation Journal, XIII (2007), No. 1, 89-95
  • [13] Fryze S., Active, reactive, and apparent power in non-sinusoidal systems, Przeglad Elektrot., (1931), No. 7, 193-203. (In Polish)
  • [14] Ferrero A., Definitions of Electrical Quantities Commonly Used in Non-Sinusoidal Conditions, European Trans. on Electrical Power, 8 (1988), 235-240
  • [15] C.I. Budeanu, “Reactive and fictitious powers,” Inst. Romain de I’Energie, Bucharest, Rumania, 1927. (In Romanian)
  • [16] Popescu Mihaela, Bitoleanu A., Dobriceanu M., On the current decomposition based on instantaneous apparent power vector, Proc. of the Tenth IASTED International Conf. on Power and Energy Systems, Acta Press, Baltimore, 2008, 120-125
  • [17] Peng F.Z. and Tolbert L.M., Compensation of nonactive current in power systems - definitions from a compensation standpoint, IEEE Power Engineering Society Summer Meeting, July 15-20 (2000), Seattle, WA, 983-987
  • [18] Czarnecki L.S., Limitation of the IRP p-q Theory as Control Algoritm of Switching Compensators, 9th International Conference, Electrical Power Quality and Utilisation, Barcelona, 9-11 October 2007