An Improved Method for Voltage Sag Detection Based on Weighted Least-Squares Estimation with Harmonic Models

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Ulepszona metoda detekcji zapadów napięcia bazująca na określaniu wartości ważonej najmniejszych kwadratów z uwzględnieniem harmonicznych
Języki publikacji
EN
Abstrakty
EN
A rapid voltage sag detection method based on weighted least-squares estimation (WLSE) with harmonic models is proposed to satisfy the requirement of the dynamic voltage restorer. The covariance resetting technique is adopted to detect the voltage sag accurately and rapidly, even in condition the voltage contains considerable amount of harmonic components. The threshold of covariance resetting is larger than the steady state error between the sample and estimation of the voltage for the purpose of favorable covariance resetting only if the voltage sag occurs. The threshold of covariance resetting can be small because the steady state error will contain little harmonic components by the proposed WLSE method which have a positive impact on the detecting speed even if the depth of voltage sag is low. The algorithm has been tested under different conditions so as to verify its performance on voltage sag detection.
PL
Zaproponowano metodę szybkiej detekcji zapadu napięcia bazująca na określaniu średniej ważonej najmniejszych kwadratów. Do detekcji zapadu wykorzystuje się technikę kowariancji co umożliwia szybką detekcję nawet przy znacznej zawartości harmonicznych. (Ulepszona metoda detekcji zapadów napięcia bazująca na określaniu wartości ważonej najmniejszych kwadratów z uwzględnieniem harmonicznych)
Rocznik
Strony
238--241
Opis fizyczny
Bibliogr. 11 poz., rys., tab.
Twórcy
autor
autor
autor
autor
autor
Bibliografia
  • [1] Bollen. M, Understanding Power Quality Problems: Voltage Sags and Interruptions, New York, IEEE Press, 1999.
  • [2] Jimichi T, Fujita H, Akagi H, Design and experimentation of a dynamic voltage restorer capable of significantly reducing an energy-storage element, IEEE Trans. Ind. Applications, 44(2008), No.3, 817-825.
  • [3] Meyer C, Doncker R, Li Y W, et al. Optimized control strategy for a medium-voltage DVR—theoretical investigations and experimental results, IEEE Trans. Power Electron., 23(2008),No.6, 2746-2754.
  • [4] Nielsen J G, Newman M, Nielsen H, et al. Control and testing of a dynamic voltage restorer (DVR) at medium voltage level, IEEE Trans. Power Electron., 19(2004), No.3, 806-813.
  • [5] Juárez. E. E, Hernández. A, An analytical approach for stochastic assessment of balanced and unbalanced voltage sags in large systems, IEEE Trans. Power Delivery, 21(2006),No.3, 1493-1500.
  • [6] Bollen. M, Algorithms for characterizing measured three-phase unbalanced voltage dips, IEEE Trans on Power Delivery, 18(2003), No.3, 937-944.
  • [7] Zhou Hui, Qi Zhiping, A survey on detection algorithm and restoring strategy of dynamic voltage restorer, Power System Technology, 30(2006), No.6, 23-29.
  • [8] Amaris. H, Alvarez. C, Alonso. M, et al. Computation of voltage sag initiation with fourier based algorithm, kalman filter and wavelets, IEEE Conference on PowerTech, 2009.
  • [9] Bae .B, Lee. J, Jeong. J, et al. Line-interactive single-phase dynamic voltage restorer with novel sag detection algorithm, IEEE Trans. Power Delivery, 25(2010), No.4, 2702-2709.
  • [10] Song. H. S, Nam. K, Mutschler. P, Very fast phase angle estimation algorithm for a single-phase system having sudden phase angle jumps, IEEE Industry Applications Society Annual Meeting, 2002.