Identyfikatory
Warianty tytułu
The rules of drive system's selection with medium voltage's frequency converter and induction cage motor with nominal parameters of: power 3150 kW, voltage 6 kV, frequency 72,5 Hz for a water supply pumps
Języki publikacji
Abstrakty
In this paper, the criteria for the selection elements of the drive system water supply pump are presented. Currently, drive system with fluid coupling is used, which make a base for creating a new type of drive systems. Considered drive systems consists of squirrel-cage motor medium volatge and medium voltage invertor. The selection was dependent on qualitative and quantitative criteria, which describe technical, operating and economic properties. There were described three types of drive systems with medium volatge invertor. Moreover, application of new drive system with fluid coupling VORECON was considered. Based on charactristics of selected pump and predicted working point, calculated power input of drive systems, energy efficiency and distortion factor of input current. Obtained results allowed to quantify of mentioned drive systems. Further evaluation could be made based on propertis of drive system not inclued in this study. Presented method of drive system selection could be useful in practice design.
Czasopismo
Rocznik
Tom
Strony
105--110
Opis fizyczny
Bibliogr. 2 poz., rys., tab.
Twórcy
Bibliografia
- [1]. Koczara W., Szulc Z.: Analiza techniczno – ekonomiczna zastosowania układów falownikowych do pompy wody zasilającej dla kotła 420ton pary/h. Praca umowna dla przemysłu. ISEP PW. Warszawa, Marzec 2009.
- [2]. Przybylski J., Szulc Z.: Doświadczenie eksploatacyjne napędów pomp dużych mocy z silnikami zasilanymi z przemienników częstotliwości średniego napięcia 6kV – efektywność eksploatacji napędów regulowanych dużych mocy. Maszyny Elektryczne. Zeszyty Problemowe Nr 78/2007 EENSE. Komel, Katowice.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BPS2-0055-0074