PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Accurate fault location in three-terminal overhead lines using two-end synchronized measurements of voltage and current phasors

Identyfikatory
Warianty tytułu
PL
Dokładna lokalizacja zwarć w napowietrznych liniach z odgałęzieniem z użyciem pomiarów synchronicznych fazorów napięć i prądów z dwóch końców linii
Języki publikacji
EN
Abstrakty
EN
This paper deals with fault location in three-terminal overhead lines by means of two-end synchronized measurements. The delivered fault location algorithm consists of three subroutines, designated for locating the faults in particular line section and the procedure of selecting the valid subroutine. All subroutines are formulated for the natural fault loops, which is distinct from the up-to-date approach. This has been applied with the aim of minimising the adverse influence of uncertainty with respect to impedance data of equivalent sources behind the line terminals upon the fault location accuracy. The selected results of fault location accuracy evaluation performed with the use of fault data obtained from ATP-EMTP simulations are presented and discussed.
PL
W artykule rozpatrzono lokalizację zwarć w liniach napowietrznych z odgałęzieniem z użyciem synchronicznych pomiarów na dwóch końcach linii. Przedstawiony algorytm składa się z trzech procedur lokalizacji, przeznaczonych do lokalizacji zwarć w poszczególnych sekcjach linii, oraz procedury wyboru obowiązującej procedury lokalizacji. W odróżnieniu od dotychczas stosowanego podejścia, wszystkie procedury lokalizacji zostały sformułowane dla naturalnych pętli zwarciowych. Zastosowano to w celu ograniczenia niekorzystnego wpływu niepewności danych w odniesieniu do inipedancji ekwiwalentnych podsystemów z końców linii na dokładność lokalizacji. Zamieszczono i omówiono wybrane rezultaty analizy dokładności lokalizacji zwarć, przeprowadzonej z użyciem przebiegów uzyskanych z symulacji zwarć z pomocą programu ATP-EMTP.
Rocznik
Strony
213--228
Opis fizyczny
Bibliogr. 13 poz., rys., tab.
Twórcy
autor
autor
Bibliografia
  • 1. Kacejko R, Machowski J.: Zwarcia w systemach elektro-energetycznych (Faults in eleetric power systems - in Polish). Wydawnictwa Naukowo-Techniczne, Warszawa, 2002.
  • 2. Ziegler G. (coordinator): Application guide on protection of complex transmission network configurations. CIGRE materials - SC-34 WG-04. August, 1990.
  • 3. Aggarwal R. K., Coury D. V., Johns A. T, Kalam A:. A practical approach to aceurate fault location on extra high voltage teed feeders. IEEE Transactions on Power Delivery. Vol. 8, No. 3, July 1993, pp. 874-883.
  • 4. Girgis A., Hart D. G., Peterson W.: A new fault location technique for two and three terminal lines. IEEE Transactions on Power Delivery. Vol. 7, No. 1, January 1992, pp. 98-107.
  • 5. Girgis A. A., King D.: Fault location in distribution feeders in the presence of distributed generation. Proccedings of Study Committee B5 Colloquium. Sydney, Australia, 30.09-1.10. 2003, paper 217.
  • 6. Iżykowski J., Moląg R., Rosołowski E., Saha M. M.: Fault location in three-terminal line with use of limited measurements. Proceedings of PowerTech (CD). St. Petersburg, 27-30.06.2005.
  • 7. Ying-Hong Lin, Chih-Wen Liu, Chi-Shan Yu: A new fault locator for three-terminal transmission lines - using two-terminal synchronized voltage and current phasors. IEEE Transactions on Power Delivery. Vol. 17, No. 2, April 2002, pp. 452-459.
  • 8. Wiszniewski A.: Accurate fault impedance locating algorithm. IEE Proceeding. Part C, Vol. 130, No. 6, 1983, pp. 311-315.
  • 9. Eriksson L., Saha M. M., Rockefeller G. D.: An accurate fault locator with compensation for apparent reactance in the fault resistance resulting from remote-end infeed. IEEE Transactions on PAS. Vol. 104, No.2, February 1985, pp. 424-436.
  • 10. Iżykowski J., Rosołowski E., Saha M. M.: Locating faults in parallel transmission lines under availability of complete measurements at one end. IEE Generation Transmission and Distribution. Vol. 151, No. 2, March 2004, pp. 268-273.
  • 11. Iżykowski J., Moląg R., Rosołowski E., Saha M. M.: Accurate location of faults on power transmission lines with use of two-end unsynchronized measurements. IEEE Transactions on Power Delivery. Vol. 21, No. 2, April 2006, pp. 627-633.
  • 12. Iżykowski J., Rosołowski E., Saha M. M., Balcerek P:. Accurate algorithm for locating faults in power transmission lines under saturation of current transformers, Proceedings of PSCC (CD). Liege. 22-26.08.2005.
  • 13. Dommel H.: Electro-Magnetic Transients Program. BPA, Portland, Oregon, 1986.