PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Partial discharges behaviour in a rod-plane arrangement with an insulating barrier

Identyfikatory
Warianty tytułu
PL
Wyładowania niezupełne w układzie elektrod pręt-płyta z przegrodą izolacyjną
Języki publikacji
EN
Abstrakty
EN
Apparent charge and surface charge density have been measured under AC voltage in a rod-plane arrangement with a dielectric barrier. It is shown from our study that apparent charge characteristics depend on the position of the barrier in the rod-plane air gap and that partial discharges (PD) activity is minimum when the barrier touches the rod electrode. The influence of the barrier width and its thickness was also investigated. The measurement of the surface charge density in the vicinity of the plane electrode was achieved by means of a capacitive probe, with different positions of the barrier in the rod-plane air gap.
PL
W artykule opisano wyniki pomiarów ładunku pozornego oraz gęstości ładunku powierzchniowego występujących przy napięciu przemiennym w układzie elektrod pręt-płyta z przegrodą izolacyjną. Z badań wynika, że charakterystyki ładunku pozornego zależą od miejsca umieszczenia przegrody w odstępie między elektrodami w powietrzu i że poziom wyładowań niezupełnych (PD) jest najmniejszy gdy przegroda dotyka elektrody prętowej. Badano także wpływ szerokości i grubości przegrody. Pomiary gęstości ładunku powierzchniowego w pobliżu elektrody płaskiej wykonywano przy użyciu sondy pojemnościowej, dla różnych pozycji przegrody w odstępie powietrznym pręt-płyta.
Rocznik
Strony
187--196
Opis fizyczny
Bibliogr. 6 poz., rys., tab.
Twórcy
autor
autor
  • Laboratoire de Génie Électrique. de Bejaia, Université A.MIRA Bejaia. Algeria, ms8570@yahoo.com
Bibliografia
  • 1. Guillermin C: La degradation des isolants électriques. Degradation of insulating electric materials. LEMD- E Schneider Electrique, P1-4, 1999.
  • 2. Beroual A., Boubakeur A.: Influence of barrier on the lightning and switching impulse strength of mean air gaps in point /plane arrangements. IEEE Trans. Electr. Insl., 26, (6), 1991, pp. 1130-1139.
  • 3. Ming Li., Leijon M., Bengston T.: Factors influencing barrier effects in air-gaps. Proc 9th Int. Symp. on High Voltage Engineering ISH. Graz 1995, pp. 2168 (1-4).
  • 4. Mouhoubi S., Boubakeur A.: Electric field measurement in point-plane air gap with insulating barrier under AC voltage. SSD(IEEE). Tunisia, PES113, 2005.
  • 5. Mouhoubi S., Boubakeur A.: Measurement of electric field strength in a point-barrier with a hole-plane arrangement. 4'h International. Conf. On Electric charges in Non-conductive Materials CSC4, France 2001, pp. 317-320.
  • 6. Boubakeur A., Mokhnache L., Boukhtache S., Feliachi A.: Theoretical investigation on barrier effect on rod- plane air gap breakdown voltage based on streamer criterion. IEE Proc- Sci. Meas. Technol., 151, (3), 2004, pp. 167-174.