Dependence of the striking distance on earth electrode shape: a laboratory investigation

Identyfikatory
Warianty tytułu
PL
Wpływ kształtu elektrod uziemieniowych na długość drogi przeskoku: badania laboratoryjne
Języki publikacji
EN
Abstrakty
EN
The electrogeometric model is now widely used for the dimensioning of lightning protection systems of ground structures. This model has the advantage of taking into account the magnitude of the lightning current and its statistical distribution but has a weakness in that it does not include the shape of electrode of the ground structure. This paper describes a laboratory experiment to investigate the dependence of the striking distance of a descending negative discharge on the shape of the ground electrode/structure. A theoretical study, based on the Lemke streamer-leader model, is also described. In this study, the streamer discharge is assumed to grow into a stable leader in the space between two electrodes when the streamer reaches a critical length, associated with the shape and polarity of the energized electrode. The experimental model uses an air-water interface in which the water conductivity is varied. The experimental results agree with the theoretical predictions.
PL
W projektowaniu układów ochrony odgromowej budowli naziemnych wykorzystuje się szeroko modele elektryczno-geometryczne. Ich zaletą jest możliwość uwzględnienia wartości prądu wyładowania i jego rozkładu statystycznego, wadą - niemożliwość analizy wpływu kształtu elektrod uziemieniowych. Artykuł przedstawia badania laboratoryjne zależności długości drogi przeskoku udaru o biegunowości ujemnej od kształtu elektrody uziemieniowej. Przedstawiono również analizę teoretyczną problemu w oparciu o model strimerowo-liderowy Lemkego. W analizie tej założono, że wyładowanie strimerowe przechodzi w ustabilizowane wyładowanie liderowe w przestrzeni międzyelektrodowej gdy strimer osiąga długość krytyczną, zależną od kształtu i biegunowości elektrody uziemieniowej. W modelu laboratoryjnym wykorzystano układ woda-powietrze ze zmienną konduktywnością cieczy. Wyniki badań laboratoryjnych są zgodne z analizą teoretyczną.
Rocznik
Strony
127--142
Opis fizyczny
Bibliogr. 20 poz., tab., rys.
Twórcy
autor
  • High Voltage Laboratory, University of Béjaia, Targa - Ouzemmour, Algeria
autor
  • High Voltage Group, School of Engineering, Cardif University, UK
autor
  • Hochschule fur Technik, Wirtschaft und Sozialewesen, FHT, Zittau, Germany
autor
  • Institute of Electronics, University of Tizi-Ouzou, Algeria
Bibliografia
  • 1. Boudissa R., Pi11ing J.: Modelluntersuchungen zum Einfluss Von Fangentladungen auf die Blitzeinschlagwahrscheinlichkeit. 20. Internationale Blitzschutzkonferenz, S. 2.5/1 - 2.5/4, Interlaken, Schweiz; 1990.
  • 2. Boudissa R., Berndt L.: Theoretical and experimental inwstigation on the influence of up-ward leader on the efficiency of lighlning protection eąuipment. 21st International Conference on Lightning Protection (ICLP), Paper No.2.06, Berlin, Germany, 1992, pp.61-64.
  • 3. Hasse P., Wiesinger J.: Handbuch fur Blitzschutz und Erdung Pflaum Verlag. Miinchen; Germany, 1992.
  • 4. Le groupe des Renardi res: L’amorcage en polarite negative des grands intervalles d'air aux renardi res. Electra 74, 1981, pp. 72-216.
  • 5. Hofbauer F.: Die Ausfuhrung Von Blitzeinrichtungen in Hochspannungsanlagen. 19. Internationale Blitzschutzkonferenz, S. 125-134, Graz, Ósterreich, 1988.
  • 6. Pi11ing J.: Zum Problem des Primdrblitzschutzes Umspannwerken unter Beriicksichtigung von Fangentladungen. 19. Internationale Blitzschutzkonferenz, S.75-77, Graz, Ósterreich, 1988.
  • 7. Cortina R et al.: Some aspects of the evaluation of the lightning performance of the electricał systems. CIGRE WG 33.01, 1980.
  • 8. Suzuki T., Myake K., Shindo T.: Discharge path model in model test of lightning strokes to smali mast. IEEE Trans. PAS, Vol.PAS-100, No.7, 1981, pp. 3551-3561.
  • 9. Lemke E.: Beitrag zur Abschdtzung der Durchschlagspannung langer Luftfunkenstrecken. Zeitschrift fur IET, Vol. 3, Leipzig, Germany, 1974, pp. 186-192.
  • 10. Lemke E.: Calibration procedure for the streamer leader model with respect to the predetermination of the SI strength of long air gaps. CIGRE - SC 33 - WG01, 28 IWD, 1985.
  • 11. Lemke E.: Die Leaderentladung und ihre Bedeutung fur das Durchschlagverhalten langer Luftfunkenstrecken. Wiss. Zeitung Elektrotechnik, Vol.l3, 1969, pp. 77-91.
  • 12. Lemke E.: Vorausberechnung der Durchschlagspannung langer Luftisolierstrecken bei Belasiung mit Schallimpulsspannungen kritischer Stirnzeit. Elektrie, Vol. 40, 1986, pp 222-224.
  • 13. Lemke E.: Der Durchschlagmechanismus von Luftfunkenstrecken bei Schaltspannungen. Wissenschaftliche Zeitschrift der Technischen Universitat Dresden, Heft 1, Dresden, Germany, 1968, pp.105-115.
  • 14. Erler F.: Zum Kriechiiberschlag dicker Isolatoren bei Wechselspannung. Elektrie, Vol. 3, Berlin (Germany), 1969, pp. 100-102.
  • 15. Voss W.: Untersuchungen zur Entwicklungparalleler Entladungen beim StoƁspannungsdurchschlag in Gasen. Diss. A TU Carolo-Wilhelmina, Braunschweig, 1979.
  • 16. Boudissa R., Djafri S., Be1aicha R.: Influence of the electrical structures form on iheir striking probability. 10th International Symposium of High Voltage Engineering, Paper 315, Montreal, Canada, 1997.
  • 17. Erler E.: Neue Erkenntnisse uber die Vorlichtbogenverlangerung wahrend des Kriechuberschlages dicker Isolatoren bei Impuls - und Wechselspannung. Diss. A TU Dresden, Germany, 1968.
  • 18. Zhirh M.: Modelluntersuchungen zum Schaltspannungsuberschlag langer Isolatoren mit leitfahigen Oberflachenbelag. Diss. A TU Dresden, Germany, 1989.
  • 19. Horvath T.: Computation of lightning protection. Research Studies Press LTD; Taunton, 1991.
  • 20. Boudissa R., Belaicha R., Boubakeur A.: Experimental and theoretical study of the influence lightning conductor's form on its zone of protection. 24th International Conference on Lightning protection (ICLP), Birmingham; UK, 1998.
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BPS2-0035-0032
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.