The insulation of converter transformer is stressed by AC and DC voltages. To investigate partial discharge (PD) characteristic of oilpaper insulation, this paper designed a power source system of DC superimposed AC voltage. The testing sample is an air gap model in the middle of an insulation cardboard. A broadband current transformer is used to measure PD current recorded by an oscilloscope with a bandwidth of 5 GHz. Experiments are performed under AC,DC only, and DC superimposed AC voltages with the sample immersed in transformer oil using electrode configurations that is parallel plate. The single PD pulses are anglicized by ORIGIN software. It is realized that the impulse current signals generated due to partial discharges under AC and DC voltages are different with amplitude, rise time, counts, duration and energy content PD pulse under AC voltage is of long duration pulse compared to that generated under DC voltage, and the PD pulse under DC superimposed AC voltage is stochastic. The key point is the moment (phase position) PD occurring moves to the zero point of the applied voltage than the case only under ac voltage. These will contribute to the development of effective PD monitoring systems for oil-insulated converter transformer.
PL
Izolacja transformatorów w przekształtnikach jest narażona na napięcia AC i DC. Przeprowadzono analizę wyładowań niezupełnych w izolacji z papieru olejowego w systemach napięcia stałego z obecnością składowej przemiennej. Zarejestrowano wyładowania przy użyciu oscyloskopu o paśmie 5 GHz. Badania przeprowadzona dla napięcia DC, AC oraz DC plus AC. Impulsy prądu wyładowań mają inną amplitudę, czas narastania i energię w zależności od rodzaju napięcia. Istotną sprawą jest napięcia. Zaproponowano efektywna metodą monitorowania jakości izolacji transformatorów w przekształtnikach.
Rocznik
Strony
312--318
Opis fizyczny
Bibliogr. 16 poz., wykr., schem.
Twórcy
autor
autor
autor
autor
autor
Bibliografia
  • [1] Kaim, L. For Oil Immersed HVDC Converter Transformers, IEEE Std C57.129-1999, IEEE USA.
  • [2] KENNEDY, W. Recommended Dielectric Tests and Test Procedures for Converter Transformers and Smoothing Reactors, IEEE Trans. Power Deliv. PD-1 (1986), 161–166.
  • [3] DARLEY, V. : Partial Discharges within Transformers and the Use of Ultrasonic Techniques in their Location, Proc. IEE coll., London, UK, 6 December 1991, publ.184, pp. 7/1–7/3.
  • [4] A. Cavallini, G. C. Montanari, F. Puletti and A. Contin, “A new methodology for the identification of PD in electrical apparatus: properties and applications”, IEEE Trans. Dielectr. Electr. Insul., Vol. 12, pp. 203-214, 2005.
  • [5] POMPILI, M. MAZZETTI, C. BARTNIKAS, R. : Partial Discharge Pulse Sequence Patterns and Cavity Development Times in Transformer Oils under ac Conditions, IEEE Trans. Diel. Electr. Insul. DEI-12 (2005), 395–403.
  • [6] A. Cavallini, G.C. Montanari, and F. Puletti, “A Fuzzy logic algorithm to detect electrical trees in polymeric insulation systems”, IEEE Trans. Dielectr. Electr. Insul., Vol. 12, pp. 1134- 1144, 2005.
  • [7] KWEON, D. J. CHIN, S. B. KWAK, H. R. KIM, J. C. SONG, K. B. : The Analysis of Ultrasonic Signals by Partial Discharge and Noise from the Transformer, IEEE Trans. Power Deliv. PD-20 (2005), 1976–1983.
  • [8] CAVALLINI, A. MONTANARI, G. C. CIANI, F. : Analysis of Partial Discharge Phenomena in Paper Oil Insulation Systems as a Basis for Risk Assessment Evaluation, Proc. IEEE Intern. Conf. Diel. Liquids, Coimbra, Portugal, 26 June–1 July 2005, 241–244.
  • [9] S. Wenrong, L. Junhao, Y. Peng, H. Haibo and L. Yanming, “Measurement and analysis for pulse current shapes of partial discharge in oil under DC voltage”, J. Xi’an Jiaotong University, Vol. 42, No. 4, pp. 481-486, 2008 (In Chinese).
  • [10] P. H. F. Morshuis, and J. J. Smit, “Partial discharge at dc voltage: their mechanism, detection and analysis”, IEEE Trans. Dielectr. Electr. Insul., Vol. 12, pp. 328-340, 2005.
  • [11] G. Hoogenraad and J. Beyer, “Digital HVDC partial discharge testing”, IEEE Intern. Sympos. Electr. Insul., Anaheim, CA, USA, pp. 448-451, 2000.
  • [12] P. Morshuis and J. Beyer, “Quality assessment of HVDC components by PD analysis”, IEEE Conf. Electr. Insul. Dielectr. Phenomena, Minneapolis, USA, pp. 542-545, 1997.
  • [13] G. Hoogenraad, P.H.P. Morshuis, and C. Petrarca, “Classification of partial discharges for DC equipment,” IEEE Electrical Insulation and Dielectric Phenomena, San Francisco, USA, pp. 110-112, 1996.
  • [14] ASTM, “Standard test method for dielectric breakdown voltage and dielectric strength of solid electrical insulating materials under Direct-voltage stress”, Standard D 3755 -86 (re-approved 1990), 1986.
  • [15] Cleary, G.P., Judd, M.D., and Farish, O. “Investigation of partial discharge current pulses in transformer insulating oil”. Proc. Int. Conf. on Advances in Processing, Testing and Application of Dielectric Materials, Wroclaw, Poland, September 2001, pp. 50–53
  • [16] IEEE Standard, The IEEE Standard Dictionary of Electrical and Electronics Terms, IEEE Std 100, Sixth Edition, IEEE, Inc., 1996.