PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Protection of Electrical and Electronic Systems against Surges by an Isolation Transformer

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Wykorzystanie transformatorów separujących do ochrony przed udarami systemów elektrycznych i elektronicznych
Języki publikacji
EN
Abstrakty
EN
Surges due to flashes to and near a line, are one of the main causes of damage to equipment of the electrical and electronic systems within a structure. Simplified formulae are given for an approximated evaluation of the number of considered surges. The effectiveness of singlephase double screen isolation transformer in the attenuation of common mode transient voltage is investigated. Tests were performed with its ungrounded and grounded screens. It is shown that a not correct grounding of the transformer screen may eliminate the effect of protection.
PL
Przepięcia wywołane przez wyładowania piorunowe w sąsiedztwie linii są jedną z podstawowych przyczyn uszkodzeń urządzeń systemów elektrycznych i elektronicznych. Podano uproszczone zależności do wyznaczania liczby analizowanych udarów. Badano właściwości jednofazowego podwójnie ekranowanego izolacyjnego transformatora. Pomiary przeprowadzono ekranem uziemionym lub nieuziemionym. Wykazano, że nieprawidłowo uziemiony ekran transformatora może wyeliminować efekt ochrony.
Rocznik
Strony
11--13
Opis fizyczny
Bibliogr. 8 poz., tab., wykr., schem.
Twórcy
autor
autor
autor
autor
autor
autor
Bibliografia
  • [1] IEC 62066/TR: “General basic information regarding surgeovervoltage and surge protection in low-voltage AC power systems”, Ed. 1.0, 2001.
  • [2] IEC 62305-2: “Protection against lightning – Riskmanagement”, First Edition, January 2006
  • [3] IEC 62305-4: “Protection against lightning – Electrical and electronic systems within structures”, First Edition, January 2006.
  • [4] IEC 62305-2: “Protection against lightning – Riskmanagement”, Second Edition, CDV, October 2009
  • [5] Johannesen S.T., Huse J., Johanse H.: “Statistical analyses offire damages in relation to lightning”, Proceedings of XXII ICLP, Budapest 1994.
  • [6] Nucci C.A. et al.: ”Lightning induced voltages on over head power lines” CIGRE WG 33-01-Electra No. 162, October 1995.
  • [7] Popolansky F., Prochazka F., Schlamp M.: “Frequency distribution of peak values of lightning over voltages in a rurallow-voltage network”, Proceedings of XXI ICLP, Berlin 1992.
  • [8] Pomponi R., Kijima H., Parente M., Popp E., Scott W.A,Zeddam A.: "Surge voltages and currents measured ontelecommunication subscriber lines", EMC Symposium Zurich,March 1993
Typ dokumentu
Bibliografia
Identyfikator YADDA
bwmeta1.element.baztech-article-BPOM-0023-0017
JavaScript jest wyłączony w Twojej przeglądarce internetowej. Włącz go, a następnie odśwież stronę, aby móc w pełni z niej korzystać.