Nowa metoda lokalizacji źródła zapadu napięciowego na przykładzie sieci brazylijskiej
Języki publikacji
Abstrakty
This article presents a novel method to locate the voltage sag source based on directional overcurrent (DOC) relay information. In this method the source of voltage sag is located by using the variation of magnitude of measured current positive-sequence component during sag and presag conditions and the sign of its phase-angle jump. The performance of the proposed method is compared with distance relay (DR) and phase change in sequence current (PCSC) methods by using PSCAD/EMTDC on a simulated case study. The results show the good and unique performance of the novel method in cases where only currents are recorded.
W artykule zaprezentowano nową metodę lokalizacji źródła zapadu napięcia bazującej na informacji o kierunkowym przeciążeniu prądowym. Źródło zapadu napięcia jest lokalizowane na podstawie pomiaru amplitudy i fazy prądu w czasie zapadu i przed zapadem. Porównano metodę z z dotychczas stosowanymi metodami DR i PCSC.
Wydawca
Czasopismo
Rocznik
Tom
Strony
112--115
Opis fizyczny
Bibliogr. 11 poz., schem., tab.
Twórcy
autor
autor
autor
- Department of Electrical Engineering, Bu Ali Sina University, Hamedan, Iran, Mh_moradi@yahoo.co.uk
Bibliografia
- [1] IEEE Std 1159, 1995, Recommended Practice for Monitoring Electric Power Quality.
- [2] Bollen M. H. J., Understanding Power Quality Problems: Voltage Sags and Interruptions, IEEE Press: New York, 1999.
- [3] Parsons A. D., Grady W. M., Powers E. J., Soward J. J., A Direction Finder for Power Quality Disturbances Based upon Disturbance Power and Energy, IEEE Transaction on Power Delivery, 15 (2000), No. 3, 1081–1086.
- [4] Li C., Tayjasanant T., Xu W., Liu X., Method for Voltage Sag Source Detection by Investigating Slope of the System Trajectory, IEE Proceedings-Generation, Transmission and Distribution, 150 (2000), No. 3, 367–372.
- [5] Tayjasanant T., Li C., Xu W., A Resistance Sign-based Method for Voltage Sag Source Detection, IEEE Transactions on Power Delivery, 20 (2005), No. 4, 2544-2551.
- [6] Hamzah N., Mohamed A., Hussain A., A New Approach to Locate the Voltage Sag Source Using Real Current Component, Electric Power Systems Research, 72 (2004), 113-123.
- [7] Pradhan A. K., Routray A., Applying Distance Relay for Voltage Sag Source Detection. IEEE Transactions on Power Delivery, 20 (2005), No. 1, PP: 529-531.
- [8] Leborgne R. C., Karlsson D., Daalder J., Voltage Sag Source Location Methods Performance Under Symmetrical and Asymmetrical Fault Conditions. Transmission & Distribution Conference and Exposition, Latin America, IEEE/PES, 1 (2006), No. 1, 1-6.
- [9] Gomez J., Morcos M., Tourn D., Felici M., A Novel Methodology to Locate Originating Points of Voltage Sags in Electric Power Systems.18th International Conference on Electricity Distribution, 2005.
- [10] Leborgne R. C., Karlsson D., Voltage Sag Source Location Based on Voltage Measurements Only, Electrical Power Quality and Utilisation, 14 (2008), No. 2, 25-30.
- [11] Pradhan A. K., Routray A., Madhan S., Fault Direction estimation in radial distribution system using phase change in sequence current, IEEE Transaction on Power Delivery, 22 (2007), No. 4, 2065-2071.