PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Wykorzystanie wieloczynnikowej analizy wariancji w badaniach elektryzacji strumieniowej olei izolacyjnych

Autorzy
Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
EN
The application of multifactor analysis of variance in streaming electrification of insulations oil
Języki publikacji
EN
Abstrakty
EN
The paper presents the method of a multifactor variance analysis used for the assessment of the tendency of mineral insulation oils to electrification (ECT). The conclusions are based on the results of laboratory investigations of streaming electrification of an oil sample carried out in a laboratory model system with a spinning disk. The influence of the rotational speed of a disk and the degree of its surface coarseness on the current value registered was analyzed. This method can be successfully applied in diagnostics of the insulation condition of power appliances, carried out on real objects (mainly power transformers).
PL
Artykuł prezentuje metodę wieloczynnikowej analizy wariancji w zastosowaniu do oceny tendencji do elektryzacji mineralnych olejów izolacyjnych (ECT). Wnioski oparto na wynikach badań laboratoryjnych elektryzacji strumieniowej próbki oleju, wykonanych w laboratoryjnym układzie modelowym z tarczą wirującą. Analizie poddano wpływ prędkości obrotowej tarczy oraz stopień chropowatości jej powierzchni na rejestrowaną wartość prądu. Przedstawiona metoda może być z powodzeniem stosowana w diagnostyce stanu izolacji urządzeń elektroenergetycznych, wykonywanych na obiektach rzeczywistych (głównie transformatorach energetycznych).
Rocznik
Strony
39--41
Opis fizyczny
Bibliogr. 9 poz., rys., wykr.
Twórcy
autor
autor
  • Politechnika Opolska, Instytut Elektroenergetyki, ul. Prószkowska 76 B2, 45-758 Opole Opole, E-mail: s.wolny@po.opole.pl, s.wolny@po.opole.pl
Bibliografia
  • [1] Tagaki T., Murata H. et al., Reliability improvement of 500kV large capacity power transformer, CIGRE Paper, 12-02, 1978
  • [2] Sierota A., Rungis J., Electrostatic Charging in Transformers Oils. Testing and Assessment, IEEE Trans. Dielectr. Electr. Insul., Vol. 1,1994, 840-870
  • [3] Szuta J., Kędzia J., Brzostek E. , Testing static electrification phenomenon in pressboard transformer oil insulating system, 7th International Conference on Conduction and Breakdown in Dielectric Liquids, Berlin-West, 1981, 470-474
  • [4] Lindgren S.R., Washabaugh A.P. , Zahn M., von Guggenberg P., Brubaker M., Nelson J.K., Temperature and Moisture Transient Effects on Flow Electrification in Power Transformers, CIGRE 1992 General Session, Paper 15/12-02, Paris, 1992
  • [5] Zdanowski M., Influence of Composition of Dielectric Liquid Mixtures on Electrostatic Charge Tendency and Physicochemical Parameters, IEEE Trans. on Dielect. and Elect. Ins., Vol. 15, No. 2, 2008, 527-532
  • [6] Zdanowski M., Wolny S., Electrokinetic Zeta Potential Measurements on the Insulation Oil, 5th International Conference NEET’2007, Zakopane, Poland, 12-15 June 2007, Przegląd Elektrotechniczny, 3/2008, 45-47
  • [7] Zdanowski M., Wolny S., Zmarzły D., and Boczar T., ECT of ethanol and hexane mixtures in the spinning disc system, J. Electrostatics, Vol. 65, 2007, 239-243
  • [8] Zdanowski M., Criteria of ingredient selection of insulation liquid mixtures for research on static electrification, 5th International Conference NEET’2007, Zakopane, Poland, 12-15 June 2007, Przegląd Elektrotechniczny, 3/2008, 48-51
  • [9] Zdanowski M., Wolny S., Zmarzły D. and Kędzia J., The Analysis and Selection of the Spinning Disk System Parameters for the Measurement of Static Electrification of Insulation Oils, IEEE Trans. Dielectr. Electr. Insul., Vol. 14, 2007, 480-486