PL EN


Preferencje help
Widoczny [Schowaj] Abstrakt
Liczba wyników
Tytuł artykułu

Transfer function based analysis of fast transients impact on winding insulation

Wybrane pełne teksty z tego czasopisma
Identyfikatory
Warianty tytułu
PL
Analiza wpływu szybkich stanów przejściowych na izolację uzwojeń na podstawie funkcji przenoszenia
Języki publikacji
EN
Abstrakty
EN
Transformers in electrical power systems are subjected to overvoltages generated during fast transients due to switching operations and lightning strokes. If the frequency of incoming surge voltage matches the winding one, the corresponding resonance will be excited. Therefore external fast transients occurring in power systems might trigger internal overvoltages with large maximum value in transformer windings. Overvoltages having such character have been the root cause of many power transformer failures. The paper presents an approach to the identification of sensitive zones in the transformer windings based on the measurements of overvoltages inside windings and frequency dependences of admittance of the transformer.
PL
Transformatory w układach elektroenergetycznych są poddawane działaniu przepięć generowanych podczas szybkich stanów przejściowych związanych z czynnościami łączeniowymi oraz wyładowaniami atmosferycznymi. Jeżeli częstotliwość fali napięciowej oddziałującej na uzwojenie jest równa częstotliwości własnej uzwojeń to wewnątrz transformatora może wystąpić zjawisko rezonansu. Dlatego szybkie stany przejściowe występujące w układach elektroenergetycznych mogą generować przepięcia wewnętrzne o dużych wartościach maksymalnych w uzwojeniach transformatorów. Przepięcia o takim charakterze były przyczyną awarii wielu transformatorów energetycznych. Artykuł przedstawia propozycję identyfikacji wrażliwych obszarów w uzwojeniach transformatorów na podstawie pomiarów przepięć w uzwojeniu oraz zależności częstotliwościowych admitancji transformatora.
Rocznik
Strony
162--165
Opis fizyczny
Bibliogr. 12 poz., rys., wykr.,
Twórcy
autor
Bibliografia
  • [1] Rodrigo H. , Dang H. Q. S.: Behaviour of Transformer Windings under Surge Voltages, High Volt. Engin. Symp., 22 - 27 Aug. 1999, paper No. 1.287. P 6
  • [2] Working Group 12.07: Resonance Behaviour of High- Voltage Transformers, CIGRE Session, Paris, 29th Aug. - 6th Sept. 1984, paper 12 - 14
  • [3] Bickford J . P. , Heaton A. G. :Transient Overvoltages on Power Systems, IEE Proceedings, Vol. 133, Pt. C, No. 4, May 1986, pp. 201 - 223
  • [4] Henriksen E. E. : Study of Very Fast Transients Overvoltages in Transformers, Electra, No. 179, Aug. 1998, pp. 13 - 23
  • [5] Morched A. S., Marti L ., Brierly R. H., Lackey J. G. : Analysis of Internal Winding Stresses in EHV Generator Set-Up Transformer Failures, IEEE Trans. on Pow. Deliv., Vol. 11, No. 2, April 1996, pp. 888 - 894
  • [6] Paap G. C., Alkema A. A., Sluis L.: Overvoltages in Power Transformers Caused by No-Load Switching, IEEE Trans. on Pow. Deliv., Vol. 10, No. 1, Jan. 1995, pp. 301 - 307
  • [7] Pretorius R. E., Goosen P. V. : Practical Investigation into Repeated Failures of 400/220 kV Auto-Transformers in the Escom Network - Results and Solutions, CIGRE, Session 1984, paper 12 - 14
  • [8] Schei A., Alstad K., Sund J. B., Rian W.: Resonant Overvoltages in Power Station Transformers Initiated by Switching Transients in the Connected Cable Network, CIGRE, Session 1984 - 29th August- 6th Sept., paper 12 - 7
  • [9] Lapworth J. A., Wilson A. : Transformer Internal Over- Voltages Caused by Remote Energisation, IEEE PES Power Africa 2007 Conference and Exposition, Johannesburg, South Africa, 16 - 20 July 2007, pp. 1 - 6
  • [10] D’Heure H. , Even A. : Contribution to Studies on an Unusual Overvoltage Phenomenon in the Tapchanger on the HV Side of a 400 kV Station Transformer, CIGRE, Session 29th Aug. - 6th Sept., 1984, paper 12 - 1
  • [11] Margolis H. B., M. Phelps J. D., Carlomagno A. A. : Experience with Part-Winding Resonance in EHV Auto- Transformers: Diagnosis and Corrective Measures, IEEE Trans. on PAS, Vol. PAS-94, No. 4, 1975, pp. 1294 – 1300
  • [12] Hori M., Nishioka M., Ikeda Y., Noguchi K., Kajimura K., Motoyama H., Kawamura T.: Internalwinding failure due to resonance overvoltage in dis tribution transformer caused by winter lightning. IEEE Trans. on Pow. Deliv., Vol. 21, No. 3, July 2003, pp. 1600-1606
Typ dokumentu